425 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)16× 400 mm²Drop: 1.42V (2.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 37.51V (78.14%)
Voltage at Load46.6 VLine Loss: 604.0 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6063.33 V (12631.94%)0.0 V10001.67 V (20836.81%)2576916.7 WDrop High
2.5 mm²24 A18 A3638.0 V (7579.17%)0.0 V6001.0 V (12502.08%)1546150.0 WDrop High
4 mm²32 A25 A2273.75 V (4736.98%)0.0 V3750.62 V (7813.8%)966343.7 WDrop High
6 mm²41 A32 A1515.83 V (3157.99%)0.0 V2500.42 V (5209.2%)644229.2 WDrop High
10 mm²57 A44 A909.5 V (1894.79%)0.0 V1500.25 V (3125.52%)386537.5 WDrop High
16 mm²76 A59 A568.44 V (1184.24%)0.0 V937.66 V (1953.45%)241585.9 WDrop High
25 mm²101 A78 A363.8 V (757.92%)0.0 V600.1 V (1250.21%)154615.0 WDrop High
35 mm²125 A97 A259.86 V (541.37%)0.0 V428.64 V (893.01%)110439.3 WDrop High
50 mm²151 A118 A181.9 V (378.96%)0.0 V300.05 V (625.1%)77307.5 WDrop High
70 mm²192 A150 A129.93 V (270.68%)0.0 V214.32 V (446.5%)55219.6 WDrop High
95 mm²232 A181 A95.74 V (199.45%)0.0 V157.92 V (329.0%)40688.2 WDrop High
120 mm²269 A210 A75.79 V (157.9%)0.0 V125.02 V (260.46%)32211.5 WDrop High
150 mm²309 A241 A60.63 V (126.32%)0.0 V100.02 V (208.37%)25769.2 WDrop High
185 mm²353 A275 A49.16 V (102.42%)0.0 V81.09 V (168.95%)20893.9 WDrop High
240 mm²415 A324 A37.9 V (78.95%)10.1 V62.51 V (130.23%)16105.7 WDrop High
300 mm²477 A372 A30.32 V (63.16%)17.7 V50.01 V (104.18%)12884.6 WDrop High
400 mm²570 A445 A22.74 V (47.37%)25.3 V37.51 V (78.14%)9663.4 WDrop High

FAQ — 425 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 500 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16× 400 mm² copper cable for 425A over 500m at 48V (voltage drop: 1.42V or 2.96%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.