550 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.37V (1.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.02V (5.06%)
Voltage at Load408.6 VLine Loss: 6068.9 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3397.71 V (818.72%)0.0 V5604.63 V (1350.51%)3236750.0 WDrop High
2.5 mm²24 A18 A2038.62 V (491.23%)0.0 V3362.78 V (810.31%)1942050.0 WDrop High
4 mm²32 A25 A1274.14 V (307.02%)0.0 V2101.74 V (506.44%)1213781.2 WDrop High
6 mm²41 A32 A849.43 V (204.68%)0.0 V1401.16 V (337.63%)809187.5 WDrop High
10 mm²57 A44 A509.66 V (122.81%)0.0 V840.69 V (202.58%)485512.5 WDrop High
16 mm²76 A59 A318.53 V (76.76%)96.5 V525.43 V (126.61%)303445.3 WDrop High
25 mm²101 A78 A203.86 V (49.12%)211.1 V336.28 V (81.03%)194205.0 WDrop High
35 mm²125 A97 A145.62 V (35.09%)269.4 V240.2 V (57.88%)138717.9 WDrop High
50 mm²151 A118 A101.93 V (24.56%)313.1 V168.14 V (40.52%)97102.5 WDrop High
70 mm²192 A150 A72.81 V (17.54%)342.2 V120.1 V (28.94%)69358.9 WDrop High
95 mm²232 A181 A53.65 V (12.93%)361.4 V88.49 V (21.32%)51106.6 WDrop High
120 mm²269 A210 A42.47 V (10.23%)372.5 V70.06 V (16.88%)40459.4 WDrop High
150 mm²309 A241 A33.98 V (8.19%)381.0 V56.05 V (13.51%)32367.5 WDrop High
185 mm²353 A275 A27.55 V (6.64%)387.5 V45.44 V (10.95%)26243.9 WDrop High
240 mm²415 A324 A21.24 V (5.12%)393.8 V35.03 V (8.44%)20229.7 WDrop High
300 mm²477 A372 A16.99 V (4.09%)398.0 V28.02 V (6.75%)16183.8 WDrop High
400 mm²570 A445 A12.74 V (3.07%)402.3 V21.02 V (5.06%)12137.8 W~ ≤5%

FAQ — 550 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 250m at 415V (voltage drop: 6.37V or 1.53%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.