550 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.64V (1.84%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.22V (6.08%)
Voltage at Load407.4 VLine Loss: 7282.7 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4077.25 V (982.47%)0.0 V6725.55 V (1620.62%)3884100.0 WDrop High
2.5 mm²24 A18 A2446.35 V (589.48%)0.0 V4035.33 V (972.37%)2330460.0 WDrop High
4 mm²32 A25 A1528.97 V (368.43%)0.0 V2522.08 V (607.73%)1456537.5 WDrop High
6 mm²41 A32 A1019.31 V (245.62%)0.0 V1681.39 V (405.15%)971025.0 WDrop High
10 mm²57 A44 A611.59 V (147.37%)0.0 V1008.83 V (243.09%)582615.0 WDrop High
16 mm²76 A59 A382.24 V (92.11%)32.8 V630.52 V (151.93%)364134.4 WDrop High
25 mm²101 A78 A244.63 V (58.95%)170.4 V403.53 V (97.24%)233046.0 WDrop High
35 mm²125 A97 A174.74 V (42.11%)240.3 V288.24 V (69.45%)166461.4 WDrop High
50 mm²151 A118 A122.32 V (29.47%)292.7 V201.77 V (48.62%)116523.0 WDrop High
70 mm²192 A150 A87.37 V (21.05%)327.6 V144.12 V (34.73%)83230.7 WDrop High
95 mm²232 A181 A64.38 V (15.51%)350.6 V106.19 V (25.59%)61327.9 WDrop High
120 mm²269 A210 A50.97 V (12.28%)364.0 V84.07 V (20.26%)48551.2 WDrop High
150 mm²309 A241 A40.77 V (9.82%)374.2 V67.26 V (16.21%)38841.0 WDrop High
185 mm²353 A275 A33.06 V (7.97%)381.9 V54.53 V (13.14%)31492.7 WDrop High
240 mm²415 A324 A25.48 V (6.14%)389.5 V42.03 V (10.13%)24275.6 WDrop High
300 mm²477 A372 A20.39 V (4.91%)394.6 V33.63 V (8.1%)19420.5 WDrop High
400 mm²570 A445 A15.29 V (3.68%)399.7 V25.22 V (6.08%)14565.4 W~ ≤5%

FAQ — 550 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 300m at 415V (voltage drop: 7.64V or 1.84%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.