550 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 10.2V (2.46%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 33.63V (8.1%)
Voltage at Load404.8 VLine Loss: 9710.2 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5436.33 V (1309.96%)0.0 V8967.4 V (2160.82%)5178800.0 WDrop High
2.5 mm²24 A18 A3261.8 V (785.98%)0.0 V5380.44 V (1296.49%)3107280.0 WDrop High
4 mm²32 A25 A2038.62 V (491.23%)0.0 V3362.78 V (810.31%)1942050.0 WDrop High
6 mm²41 A32 A1359.08 V (327.49%)0.0 V2241.85 V (540.21%)1294700.0 WDrop High
10 mm²57 A44 A815.45 V (196.49%)0.0 V1345.11 V (324.12%)776820.0 WDrop High
16 mm²76 A59 A509.66 V (122.81%)0.0 V840.69 V (202.58%)485512.5 WDrop High
25 mm²101 A78 A326.18 V (78.6%)88.8 V538.04 V (129.65%)310728.0 WDrop High
35 mm²125 A97 A232.99 V (56.14%)182.0 V384.32 V (92.61%)221948.6 WDrop High
50 mm²151 A118 A163.09 V (39.3%)251.9 V269.02 V (64.82%)155364.0 WDrop High
70 mm²192 A150 A116.49 V (28.07%)298.5 V192.16 V (46.3%)110974.3 WDrop High
95 mm²232 A181 A85.84 V (20.68%)329.2 V141.59 V (34.12%)81770.5 WDrop High
120 mm²269 A210 A67.95 V (16.37%)347.0 V112.09 V (27.01%)64735.0 WDrop High
150 mm²309 A241 A54.36 V (13.1%)360.6 V89.67 V (21.61%)51788.0 WDrop High
185 mm²353 A275 A44.08 V (10.62%)370.9 V72.71 V (17.52%)41990.3 WDrop High
240 mm²415 A324 A33.98 V (8.19%)381.0 V56.05 V (13.51%)32367.5 WDrop High
300 mm²477 A372 A27.18 V (6.55%)387.8 V44.84 V (10.8%)25894.0 WDrop High
400 mm²570 A445 A20.39 V (4.91%)394.6 V33.63 V (8.1%)19420.5 W~ ≤5%

FAQ — 550 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 400m at 415V (voltage drop: 10.2V or 2.46%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.