550 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 20.39V (2.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 33.63V (4.87%)
Voltage at Load669.6 VLine Loss: 19420.5 W
Max Power & Breaker657.31 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5436.33 V (787.87%)0.0 V8967.4 V (1299.62%)5178800.0 WDrop High
2.5 mm²24 A18 A3261.8 V (472.72%)0.0 V5380.44 V (779.77%)3107280.0 WDrop High
4 mm²32 A25 A2038.62 V (295.45%)0.0 V3362.78 V (487.36%)1942050.0 WDrop High
6 mm²41 A32 A1359.08 V (196.97%)0.0 V2241.85 V (324.91%)1294700.0 WDrop High
10 mm²57 A44 A815.45 V (118.18%)0.0 V1345.11 V (194.94%)776820.0 WDrop High
16 mm²76 A59 A509.66 V (73.86%)180.3 V840.69 V (121.84%)485512.5 WDrop High
25 mm²101 A78 A326.18 V (47.27%)363.8 V538.04 V (77.98%)310728.0 WDrop High
35 mm²125 A97 A232.99 V (33.77%)457.0 V384.32 V (55.7%)221948.6 WDrop High
50 mm²151 A118 A163.09 V (23.64%)526.9 V269.02 V (38.99%)155364.0 WDrop High
70 mm²192 A150 A116.49 V (16.88%)573.5 V192.16 V (27.85%)110974.3 WDrop High
95 mm²232 A181 A85.84 V (12.44%)604.2 V141.59 V (20.52%)81770.5 WDrop High
120 mm²269 A210 A67.95 V (9.85%)622.0 V112.09 V (16.25%)64735.0 WDrop High
150 mm²309 A241 A54.36 V (7.88%)635.6 V89.67 V (13.0%)51788.0 WDrop High
185 mm²353 A275 A44.08 V (6.39%)645.9 V72.71 V (10.54%)41990.3 WDrop High
240 mm²415 A324 A33.98 V (4.92%)656.0 V56.05 V (8.12%)32367.5 WDrop High
300 mm²477 A372 A27.18 V (3.94%)662.8 V44.84 V (6.5%)25894.0 WDrop High
400 mm²570 A445 A20.39 V (2.95%)669.6 V33.63 V (4.87%)19420.5 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 550A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 400m at 690V (voltage drop: 20.39V or 2.95%).

What is the power capacity of 550A at 690V?

At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.