700 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.6V (0.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.56V (1.24%)
Voltage at Load687.4 VLine Loss: 3145.8 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1383.79 V (200.55%)0.0 V2282.61 V (330.81%)1677760.0 WDrop High
2.5 mm²24 A18 A830.28 V (120.33%)0.0 V1369.57 V (198.49%)1006656.0 WDrop High
4 mm²32 A25 A518.92 V (75.21%)171.1 V855.98 V (124.06%)629160.0 WDrop High
6 mm²41 A32 A345.95 V (50.14%)344.1 V570.65 V (82.7%)419440.0 WDrop High
10 mm²57 A44 A207.57 V (30.08%)482.4 V342.39 V (49.62%)251664.0 WDrop High
16 mm²76 A59 A129.73 V (18.8%)560.3 V213.99 V (31.01%)157290.0 WDrop High
25 mm²101 A78 A83.03 V (12.03%)607.0 V136.96 V (19.85%)100665.6 WDrop High
35 mm²125 A97 A59.31 V (8.59%)630.7 V97.83 V (14.18%)71904.0 WDrop High
50 mm²151 A118 A41.51 V (6.02%)648.5 V68.48 V (9.92%)50332.8 WDrop High
70 mm²192 A150 A29.65 V (4.3%)660.3 V48.91 V (7.09%)35952.0 WDrop High
95 mm²232 A181 A21.85 V (3.17%)668.2 V36.04 V (5.22%)26490.9 WDrop High
120 mm²269 A210 A17.3 V (2.51%)672.7 V28.53 V (4.14%)20972.0 WDrop High
150 mm²309 A241 A13.84 V (2.01%)676.2 V22.83 V (3.31%)16777.6 WDrop High
185 mm²353 A275 A11.22 V (1.63%)678.8 V18.51 V (2.68%)13603.5 WDrop High
240 mm²415 A324 A8.65 V (1.25%)681.4 V14.27 V (2.07%)10486.0 WDrop High
300 mm²477 A372 A6.92 V (1.0%)683.1 V11.41 V (1.65%)8388.8 WDrop High
400 mm²570 A445 A5.19 V (0.75%)684.8 V8.56 V (1.24%)6291.6 WDrop High

FAQ — 700 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 80m at 690V (voltage drop: 2.6V or 0.38%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.