⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

900 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 10.01V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 82.54V (19.89%)
Voltage at Load405.0 VLine Loss: 15600.6 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A13343.72 V (3215.35%)0.0 V22010.9 V (5303.83%)20800800.0 WDrop High
2.5 mm²24 A18 A8006.23 V (1929.21%)0.0 V13206.54 V (3182.3%)12480480.0 WDrop High
4 mm²32 A25 A5003.89 V (1205.76%)0.0 V8254.09 V (1988.94%)7800300.0 WDrop High
6 mm²41 A32 A3335.93 V (803.84%)0.0 V5502.73 V (1325.96%)5200200.0 WDrop High
10 mm²57 A44 A2001.56 V (482.3%)0.0 V3301.64 V (795.57%)3120120.0 WDrop High
16 mm²76 A59 A1250.97 V (301.44%)0.0 V2063.52 V (497.23%)1950075.0 WDrop High
25 mm²101 A78 A800.62 V (192.92%)0.0 V1320.65 V (318.23%)1248048.0 WDrop High
35 mm²125 A97 A571.87 V (137.8%)0.0 V943.32 V (227.31%)891462.9 WDrop High
50 mm²151 A118 A400.31 V (96.46%)14.7 V660.33 V (159.11%)624024.0 WDrop High
70 mm²192 A150 A285.94 V (68.9%)129.1 V471.66 V (113.65%)445731.4 WDrop High
95 mm²232 A181 A210.69 V (50.77%)204.3 V347.54 V (83.74%)328433.7 WDrop High
120 mm²269 A210 A166.8 V (40.19%)248.2 V275.14 V (66.3%)260010.0 WDrop High
150 mm²309 A241 A133.44 V (32.15%)281.6 V220.11 V (53.04%)208008.0 WDrop High
185 mm²353 A275 A108.19 V (26.07%)306.8 V178.47 V (43.0%)168655.1 WDrop High
240 mm²415 A324 A83.4 V (20.1%)331.6 V137.57 V (33.15%)130005.0 WDrop High
300 mm²477 A372 A66.72 V (16.08%)348.3 V110.05 V (26.52%)104004.0 WDrop High
400 mm²570 A445 A50.04 V (12.06%)365.0 V82.54 V (19.89%)78003.0 WDrop High

FAQ — 900 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 900A over 600m at 415V (voltage drop: 10.01V or 2.41%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.