⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

900 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.33V (0.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.01V (2.65%)
Voltage at Load411.7 VLine Loss: 5200.2 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1779.16 V (428.71%)0.0 V2934.79 V (707.18%)2773440.0 WDrop High
2.5 mm²24 A18 A1067.5 V (257.23%)0.0 V1760.87 V (424.31%)1664064.0 WDrop High
4 mm²32 A25 A667.19 V (160.77%)0.0 V1100.55 V (265.19%)1040040.0 WDrop High
6 mm²41 A32 A444.79 V (107.18%)0.0 V733.7 V (176.79%)693360.0 WDrop High
10 mm²57 A44 A266.87 V (64.31%)148.1 V440.22 V (106.08%)416016.0 WDrop High
16 mm²76 A59 A166.8 V (40.19%)248.2 V275.14 V (66.3%)260010.0 WDrop High
25 mm²101 A78 A106.75 V (25.72%)308.3 V176.09 V (42.43%)166406.4 WDrop High
35 mm²125 A97 A76.25 V (18.37%)338.8 V125.78 V (30.31%)118861.7 WDrop High
50 mm²151 A118 A53.37 V (12.86%)361.6 V88.04 V (21.22%)83203.2 WDrop High
70 mm²192 A150 A38.12 V (9.19%)376.9 V62.89 V (15.15%)59430.9 WDrop High
95 mm²232 A181 A28.09 V (6.77%)386.9 V46.34 V (11.17%)43791.2 WDrop High
120 mm²269 A210 A22.24 V (5.36%)392.8 V36.68 V (8.84%)34668.0 WDrop High
150 mm²309 A241 A17.79 V (4.29%)397.2 V29.35 V (7.07%)27734.4 WDrop High
185 mm²353 A275 A14.43 V (3.48%)400.6 V23.8 V (5.73%)22487.4 WDrop High
240 mm²415 A324 A11.12 V (2.68%)403.9 V18.34 V (4.42%)17334.0 WDrop High
300 mm²477 A372 A8.9 V (2.14%)406.1 V14.67 V (3.54%)13867.2 WDrop High
400 mm²570 A445 A6.67 V (1.61%)408.3 V11.01 V (2.65%)10400.4 WDrop High

FAQ — 900 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 80m at 415V (voltage drop: 3.33V or 0.81%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.