Kabelarea för 110 Ampere vid 100 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 100 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.73V (2.92%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 6.47V (2.81%)
Voltage at Load223.3 VLine Loss: 739.8 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A313.87 V (136.46%)0.0 V517.73 V (225.1%)34525.3 WDrop High
2.5 mm²24 A18 A188.32 V (81.88%)41.7 V310.64 V (135.06%)20715.2 WDrop High
4 mm²32 A25 A117.7 V (51.17%)112.3 V194.15 V (84.41%)12947.0 WDrop High
6 mm²41 A32 A78.47 V (34.12%)151.5 V129.43 V (56.28%)8631.3 WDrop High
10 mm²57 A44 A47.08 V (20.47%)182.9 V77.66 V (33.77%)5178.8 WDrop High
16 mm²76 A59 A29.42 V (12.79%)200.6 V48.54 V (21.1%)3236.7 WDrop High
25 mm²101 A78 A18.83 V (8.19%)211.2 V31.06 V (13.51%)2071.5 WDrop High
35 mm²125 A97 A13.45 V (5.85%)216.5 V22.19 V (9.65%)1479.7 WDrop High
50 mm²151 A118 A9.42 V (4.09%)220.6 V15.53 V (6.75%)1035.8 W~ ≤5%
70 mm²192 A150 A6.73 V (2.92%)223.3 V11.09 V (4.82%)739.8 W✓ OK (≤3%)
95 mm²232 A181 A4.96 V (2.15%)225.0 V8.17 V (3.55%)545.1 W✓ OK (≤3%)
120 mm²269 A210 A3.92 V (1.71%)226.1 V6.47 V (2.81%)431.6 W✓ OK (≤3%)
150 mm²309 A241 A3.14 V (1.36%)226.9 V5.18 V (2.25%)345.3 W✓ OK (≤3%)
185 mm²353 A275 A2.54 V (1.11%)227.5 V4.2 V (1.83%)279.9 W✓ OK (≤3%)
240 mm²415 A324 A1.96 V (0.85%)228.0 V3.24 V (1.41%)215.8 W✓ OK (≤3%)
300 mm²477 A372 A1.57 V (0.68%)228.4 V2.59 V (1.13%)172.6 W✓ OK (≤3%)
400 mm²570 A445 A1.18 V (0.51%)228.8 V1.94 V (0.84%)129.5 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 100 Meter (230V)

Vilken kabelarea krävs för 110A vid 100 meter (230V)?

För 110 Ampere över 100 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (6.73V / 2.92%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.