Kabelarea för 110 Ampere vid 150 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 150 m vid 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 5.88V (2.56%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.3V (2.74%)
Voltage at Load224.1 VLine Loss: 647.4 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A470.8 V (204.7%)0.0 V776.6 V (337.65%)51788.0 WDrop High
2.5 mm²24 A18 A282.48 V (122.82%)0.0 V465.96 V (202.59%)31072.8 WDrop High
4 mm²32 A25 A176.55 V (76.76%)53.4 V291.23 V (126.62%)19420.5 WDrop High
6 mm²41 A32 A117.7 V (51.17%)112.3 V194.15 V (84.41%)12947.0 WDrop High
10 mm²57 A44 A70.62 V (30.7%)159.4 V116.49 V (50.65%)7768.2 WDrop High
16 mm²76 A59 A44.14 V (19.19%)185.9 V72.81 V (31.65%)4855.1 WDrop High
25 mm²101 A78 A28.25 V (12.28%)201.8 V46.6 V (20.26%)3107.3 WDrop High
35 mm²125 A97 A20.18 V (8.77%)209.8 V33.28 V (14.47%)2219.5 WDrop High
50 mm²151 A118 A14.12 V (6.14%)215.9 V23.3 V (10.13%)1553.6 WDrop High
70 mm²192 A150 A10.09 V (4.39%)219.9 V16.64 V (7.24%)1109.7 W~ ≤5%
95 mm²232 A181 A7.43 V (3.23%)222.6 V12.26 V (5.33%)817.7 W~ ≤5%
120 mm²269 A210 A5.88 V (2.56%)224.1 V9.71 V (4.22%)647.4 W✓ OK (≤3%)
150 mm²309 A241 A4.71 V (2.05%)225.3 V7.77 V (3.38%)517.9 W✓ OK (≤3%)
185 mm²353 A275 A3.82 V (1.66%)226.2 V6.3 V (2.74%)419.9 W✓ OK (≤3%)
240 mm²415 A324 A2.94 V (1.28%)227.1 V4.85 V (2.11%)323.7 W✓ OK (≤3%)
300 mm²477 A372 A2.35 V (1.02%)227.6 V3.88 V (1.69%)258.9 W✓ OK (≤3%)
400 mm²570 A445 A1.77 V (0.77%)228.2 V2.91 V (1.27%)194.2 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 150 Meter (230V)

Vilken kabelarea krävs för 110A vid 150 meter (230V)?

För 110 Ampere över 150 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (5.88V / 2.56%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.