Kabelarea för 425 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 250 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 9.85V (2.46%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.24V (4.06%)
Voltage at Load390.2 VLine Loss: 7247.6 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2625.5 V (656.38%)0.0 V4330.85 V (1082.71%)1932687.5 WDrop High
2.5 mm²24 A18 A1575.3 V (393.83%)0.0 V2598.51 V (649.63%)1159612.5 WDrop High
4 mm²32 A25 A984.56 V (246.14%)0.0 V1624.07 V (406.02%)724757.8 WDrop High
6 mm²41 A32 A656.38 V (164.09%)0.0 V1082.71 V (270.68%)483171.9 WDrop High
10 mm²57 A44 A393.83 V (98.46%)6.2 V649.63 V (162.41%)289903.1 WDrop High
16 mm²76 A59 A246.14 V (61.54%)153.9 V406.02 V (101.5%)181189.5 WDrop High
25 mm²101 A78 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
35 mm²125 A97 A112.52 V (28.13%)287.5 V185.61 V (46.4%)82829.5 WDrop High
50 mm²151 A118 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
70 mm²192 A150 A56.26 V (14.07%)343.7 V92.8 V (23.2%)41414.7 WDrop High
95 mm²232 A181 A41.46 V (10.36%)358.5 V68.38 V (17.1%)30516.1 WDrop High
120 mm²269 A210 A32.82 V (8.2%)367.2 V54.14 V (13.53%)24158.6 WDrop High
150 mm²309 A241 A26.26 V (6.56%)373.7 V43.31 V (10.83%)19326.9 WDrop High
185 mm²353 A275 A21.29 V (5.32%)378.7 V35.11 V (8.78%)15670.4 WDrop High
240 mm²415 A324 A16.41 V (4.1%)383.6 V27.07 V (6.77%)12079.3 WDrop High
300 mm²477 A372 A13.13 V (3.28%)386.9 V21.65 V (5.41%)9663.4 W~ ≤5%
400 mm²570 A445 A9.85 V (2.46%)390.2 V16.24 V (4.06%)7247.6 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 425A vid 250 meter (400V)?

För 425 Ampere över 250 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (9.85V / 2.46%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.