Kabelarea för 450 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 175 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.04V (3.01%)
Voltage at Load390.3 VLine Loss: 7583.6 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1945.96 V (486.49%)0.0 V3209.92 V (802.48%)1516725.0 WDrop High
2.5 mm²24 A18 A1167.58 V (291.89%)0.0 V1925.95 V (481.49%)910035.0 WDrop High
4 mm²32 A25 A729.73 V (182.43%)0.0 V1203.72 V (300.93%)568771.9 WDrop High
6 mm²41 A32 A486.49 V (121.62%)0.0 V802.48 V (200.62%)379181.2 WDrop High
10 mm²57 A44 A291.89 V (72.97%)108.1 V481.49 V (120.37%)227508.7 WDrop High
16 mm²76 A59 A182.43 V (45.61%)217.6 V300.93 V (75.23%)142193.0 WDrop High
25 mm²101 A78 A116.76 V (29.19%)283.2 V192.6 V (48.15%)91003.5 WDrop High
35 mm²125 A97 A83.4 V (20.85%)316.6 V137.57 V (34.39%)65002.5 WDrop High
50 mm²151 A118 A58.38 V (14.59%)341.6 V96.3 V (24.07%)45501.8 WDrop High
70 mm²192 A150 A41.7 V (10.42%)358.3 V68.78 V (17.2%)32501.2 WDrop High
95 mm²232 A181 A30.73 V (7.68%)369.3 V50.68 V (12.67%)23948.3 WDrop High
120 mm²269 A210 A24.32 V (6.08%)375.7 V40.12 V (10.03%)18959.1 WDrop High
150 mm²309 A241 A19.46 V (4.86%)380.5 V32.1 V (8.02%)15167.2 WDrop High
185 mm²353 A275 A15.78 V (3.94%)384.2 V26.03 V (6.51%)12297.8 WDrop High
240 mm²415 A324 A12.16 V (3.04%)387.8 V20.06 V (5.02%)9479.5 WDrop High
300 mm²477 A372 A9.73 V (2.43%)390.3 V16.05 V (4.01%)7583.6 W✓ OK (≤3%)
400 mm²570 A445 A7.3 V (1.82%)392.7 V12.04 V (3.01%)5687.7 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 450A vid 175 meter (400V)?

För 450 Ampere över 175 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (9.73V / 2.43%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.