🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.84%
Aluminum Wire (≤3% Drop)8 AWGDrop: 7.07V (2.95%)
Voltage at Load End233.2 VLoss: 6.82 V (68.2 W)
Power & Breaker (125%)2.4 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.25 V (7.19%)222.8 V28.45 V (11.85%)172.5 WDrop/Amp High
12 AWG3.31 mm²20 A10.84 V (4.52%)229.2 V17.88 V (7.45%)108.4 W~ ≤5%
10 AWG5.26 mm²30 A6.82 V (2.84%)233.2 V11.25 V (4.69%)68.2 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A4.29 V (1.79%)235.7 V7.07 V (2.95%)42.9 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.7 V (1.12%)237.3 V4.45 V (1.85%)27.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.7 V (0.71%)238.3 V2.8 V (1.17%)17.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.35 V (0.56%)238.7 V2.22 V (0.92%)13.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.07 V (0.44%)238.9 V1.76 V (0.73%)10.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.85 V (0.35%)239.2 V1.4 V (0.58%)8.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.67 V (0.28%)239.3 V1.11 V (0.46%)6.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.53 V (0.22%)239.5 V0.88 V (0.37%)5.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.42 V (0.18%)239.6 V0.7 V (0.29%)4.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.33 V (0.14%)239.7 V0.55 V (0.23%)3.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.28 V (0.12%)239.7 V0.47 V (0.19%)2.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.24 V (0.1%)239.8 V0.39 V (0.16%)2.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (0.08%)239.8 V0.33 V (0.14%)2.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.07%)239.8 V0.29 V (0.12%)1.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.06%)239.9 V0.23 V (0.1%)1.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.05%)239.9 V0.19 V (0.08%)1.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.04%)239.9 V0.16 V (0.06%)0.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)239.9 V0.12 V (0.05%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 275 feet one-way at 240V (1-Phase), you need 10 AWG copper wire. This produces a voltage drop of 6.82V (2.84%) and delivers 233.2V at the load.

What size aluminum wire is required for 10 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 7.07V (2.95%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.