🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.8V (2.34%)
Voltage at Load End116.6 VLoss: 3.4 V (373.8 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A413.94 V (344.95%)0.0 V682.81 V (569.01%)45533.6 WDrop/Amp High
12 AWG3.31 mm²20 A260.12 V (216.77%)0.0 V429.08 V (357.56%)28613.3 WDrop/Amp High
10 AWG5.26 mm²30 A163.69 V (136.41%)0.0 V270.01 V (225.01%)18005.7 WDrop/Amp High
8 AWG8.37 mm²50 A102.87 V (85.72%)17.1 V169.68 V (141.4%)11315.4 WDrop/Amp High
6 AWG13.3 mm²65 A64.74 V (53.95%)55.3 V106.79 V (88.99%)7121.0 WDrop/Amp High
4 AWG21.15 mm²85 A40.71 V (33.92%)79.3 V67.15 V (55.96%)4478.0 WDrop/Amp High
3 AWG26.67 mm²100 A32.28 V (26.9%)87.7 V53.25 V (44.38%)3551.2 WDrop/Amp High
2 AWG33.62 mm²115 A25.61 V (21.34%)94.4 V42.24 V (35.2%)2817.1 WDrop/Amp High
1 AWG42.41 mm²130 A20.3 V (16.92%)99.7 V33.49 V (27.91%)2233.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.1 V (13.41%)103.9 V26.55 V (22.13%)1770.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.77 V (10.64%)107.2 V21.06 V (17.55%)1404.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.13 V (8.44%)109.9 V16.71 V (13.92%)1114.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.03 V (6.69%)112.0 V13.25 V (11.04%)883.5 WDrop/Amp High
250 kcmil126.7 mm²255 A6.8 V (5.66%)113.2 V11.21 V (9.34%)747.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.66 V (4.72%)114.3 V9.34 V (7.79%)623.1 W~ ≤5%
350 kcmil177.3 mm²310 A4.86 V (4.05%)115.1 V8.01 V (6.68%)534.2 W~ ≤5%
400 kcmil202.7 mm²335 A4.25 V (3.54%)115.8 V7.01 V (5.84%)467.2 W~ ≤5%
500 kcmil253.4 mm²380 A3.4 V (2.83%)116.6 V5.6 V (4.67%)373.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.83 V (2.36%)117.2 V4.67 V (3.89%)311.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.27 V (1.89%)117.7 V3.74 V (3.11%)249.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.7 V (1.42%)118.3 V2.8 V (2.34%)186.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 600 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.4V (2.83%) and delivers 116.6V at the load.

What size aluminum wire is required for 110 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.8V (2.34%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.