⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 75 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.33%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 2.87V (1.38%)
Voltage at Load End205.2 VLoss: 2.77 V (528.2 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 75 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A44.81 V (21.54%)163.2 V73.92 V (35.54%)8537.6 WDrop/Amp High
12 AWG3.31 mm²20 A28.16 V (13.54%)179.8 V46.45 V (22.33%)5365.0 WDrop/Amp High
10 AWG5.26 mm²30 A17.72 V (8.52%)190.3 V29.23 V (14.05%)3376.1 WDrop/Amp High
8 AWG8.37 mm²50 A11.14 V (5.35%)196.9 V18.37 V (8.83%)2121.6 WDrop/Amp High
6 AWG13.3 mm²65 A7.01 V (3.37%)201.0 V11.56 V (5.56%)1335.2 WDrop/Amp High
4 AWG21.15 mm²85 A4.41 V (2.12%)203.6 V7.27 V (3.49%)839.6 WDrop/Amp High
3 AWG26.67 mm²100 A3.49 V (1.68%)204.5 V5.76 V (2.77%)665.8 WDrop/Amp High
2 AWG33.62 mm²115 A2.77 V (1.33%)205.2 V4.57 V (2.2%)528.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.2 V (1.06%)205.8 V3.63 V (1.74%)418.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.74 V (0.84%)206.3 V2.87 V (1.38%)332.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.38 V (0.66%)206.6 V2.28 V (1.1%)263.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.1 V (0.53%)206.9 V1.81 V (0.87%)208.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.87 V (0.42%)207.1 V1.43 V (0.69%)165.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.74 V (0.35%)207.3 V1.21 V (0.58%)140.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.61 V (0.29%)207.4 V1.01 V (0.49%)116.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.53 V (0.25%)207.5 V0.87 V (0.42%)100.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.46 V (0.22%)207.5 V0.76 V (0.36%)87.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.37 V (0.18%)207.6 V0.61 V (0.29%)70.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.31 V (0.15%)207.7 V0.51 V (0.24%)58.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.25 V (0.12%)207.8 V0.4 V (0.19%)46.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.09%)207.8 V0.3 V (0.15%)35.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 75 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 75 feet one-way at 208V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 2.77V (1.33%) and delivers 205.2V at the load.

What size aluminum wire is required for 110 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 2.87V (1.38%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.