🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.53%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 1.15V (0.55%)
Voltage at Load End206.9 VLoss: 1.11 V (211.3 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.92 V (8.62%)190.1 V29.57 V (14.21%)3415.0 WDrop/Amp High
12 AWG3.31 mm²20 A11.26 V (5.42%)196.7 V18.58 V (8.93%)2146.0 WDrop/Amp High
10 AWG5.26 mm²30 A7.09 V (3.41%)200.9 V11.69 V (5.62%)1350.4 WDrop/Amp High
8 AWG8.37 mm²50 A4.45 V (2.14%)203.5 V7.35 V (3.53%)848.7 WDrop/Amp High
6 AWG13.3 mm²65 A2.8 V (1.35%)205.2 V4.62 V (2.22%)534.1 WDrop/Amp High
4 AWG21.15 mm²85 A1.76 V (0.85%)206.2 V2.91 V (1.4%)335.9 WDrop/Amp High
3 AWG26.67 mm²100 A1.4 V (0.67%)206.6 V2.31 V (1.11%)266.3 WDrop/Amp High
2 AWG33.62 mm²115 A1.11 V (0.53%)206.9 V1.83 V (0.88%)211.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.88 V (0.42%)207.1 V1.45 V (0.7%)167.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.7 V (0.34%)207.3 V1.15 V (0.55%)132.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.55 V (0.27%)207.4 V0.91 V (0.44%)105.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.44 V (0.21%)207.6 V0.72 V (0.35%)83.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.35 V (0.17%)207.7 V0.57 V (0.28%)66.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.29 V (0.14%)207.7 V0.49 V (0.23%)56.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.25 V (0.12%)207.8 V0.4 V (0.19%)46.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.21 V (0.1%)207.8 V0.35 V (0.17%)40.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.09%)207.8 V0.3 V (0.15%)35.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.07%)207.9 V0.24 V (0.12%)28.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.06%)207.9 V0.2 V (0.1%)23.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.05%)207.9 V0.16 V (0.08%)18.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.04%)207.9 V0.12 V (0.06%)14.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 30 feet one-way at 208V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 1.11V (0.53%) and delivers 206.9V at the load.

What size aluminum wire is required for 110 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 1.15V (0.55%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.