🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.78%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 3.83V (1.84%)
Voltage at Load End204.3 VLoss: 3.7 V (704.3 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A59.75 V (28.72%)148.3 V98.56 V (47.38%)11383.4 WDrop/Amp High
12 AWG3.31 mm²20 A37.55 V (18.05%)170.5 V61.93 V (29.77%)7153.3 WDrop/Amp High
10 AWG5.26 mm²30 A23.63 V (11.36%)184.4 V38.97 V (18.74%)4501.4 WDrop/Amp High
8 AWG8.37 mm²50 A14.85 V (7.14%)193.2 V24.49 V (11.77%)2828.8 WDrop/Amp High
6 AWG13.3 mm²65 A9.34 V (4.49%)198.7 V15.41 V (7.41%)1780.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.88 V (2.82%)202.1 V9.69 V (4.66%)1119.5 WDrop/Amp High
3 AWG26.67 mm²100 A4.66 V (2.24%)203.3 V7.69 V (3.7%)887.8 WDrop/Amp High
2 AWG33.62 mm²115 A3.7 V (1.78%)204.3 V6.1 V (2.93%)704.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.93 V (1.41%)205.1 V4.83 V (2.32%)558.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.32 V (1.12%)205.7 V3.83 V (1.84%)442.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.84 V (0.89%)206.2 V3.04 V (1.46%)351.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.46 V (0.7%)206.5 V2.41 V (1.16%)278.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.16 V (0.56%)206.8 V1.91 V (0.92%)220.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.98 V (0.47%)207.0 V1.62 V (0.78%)186.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.82 V (0.39%)207.2 V1.35 V (0.65%)155.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.7 V (0.34%)207.3 V1.16 V (0.56%)133.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.61 V (0.29%)207.4 V1.01 V (0.49%)116.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.49 V (0.24%)207.5 V0.81 V (0.39%)93.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.41 V (0.2%)207.6 V0.67 V (0.32%)77.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.16%)207.7 V0.54 V (0.26%)62.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.12%)207.8 V0.4 V (0.19%)46.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 100 feet one-way at 208V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 3.7V (1.78%) and delivers 204.3V at the load.

What size aluminum wire is required for 110 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 3.83V (1.84%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.