🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 120 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.13%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 4.6V (2.21%)
Voltage at Load End203.6 VLoss: 4.44 V (845.1 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 120 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A71.7 V (34.47%)136.3 V118.27 V (56.86%)13660.1 WDrop/Amp High
12 AWG3.31 mm²20 A45.05 V (21.66%)162.9 V74.32 V (35.73%)8584.0 WDrop/Amp High
10 AWG5.26 mm²30 A28.35 V (13.63%)179.6 V46.77 V (22.48%)5401.7 WDrop/Amp High
8 AWG8.37 mm²50 A17.82 V (8.57%)190.2 V29.39 V (14.13%)3394.6 WDrop/Amp High
6 AWG13.3 mm²65 A11.21 V (5.39%)196.8 V18.5 V (8.89%)2136.3 WDrop/Amp High
4 AWG21.15 mm²85 A7.05 V (3.39%)200.9 V11.63 V (5.59%)1343.4 WDrop/Amp High
3 AWG26.67 mm²100 A5.59 V (2.69%)202.4 V9.22 V (4.43%)1065.4 WDrop/Amp High
2 AWG33.62 mm²115 A4.44 V (2.13%)203.6 V7.32 V (3.52%)845.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.52 V (1.69%)204.5 V5.8 V (2.79%)670.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.79 V (1.34%)205.2 V4.6 V (2.21%)531.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.21 V (1.06%)205.8 V3.65 V (1.75%)421.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.75 V (0.84%)206.2 V2.89 V (1.39%)334.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.39 V (0.67%)206.6 V2.29 V (1.1%)265.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.18 V (0.57%)206.8 V1.94 V (0.93%)224.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.98 V (0.47%)207.0 V1.62 V (0.78%)186.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.84 V (0.4%)207.2 V1.39 V (0.67%)160.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.74 V (0.35%)207.3 V1.21 V (0.58%)140.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.59 V (0.28%)207.4 V0.97 V (0.47%)112.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.49 V (0.24%)207.5 V0.81 V (0.39%)93.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.39 V (0.19%)207.6 V0.65 V (0.31%)74.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.29 V (0.14%)207.7 V0.49 V (0.23%)56.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 120 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 120 feet one-way at 208V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 4.44V (2.13%) and delivers 203.6V at the load.

What size aluminum wire is required for 110 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 4.6V (2.21%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.