🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 40 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.71%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 1.53V (0.74%)
Voltage at Load End206.5 VLoss: 1.48 V (281.7 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 40 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A23.9 V (11.49%)184.1 V39.42 V (18.95%)4553.4 WDrop/Amp High
12 AWG3.31 mm²20 A15.02 V (7.22%)193.0 V24.77 V (11.91%)2861.3 WDrop/Amp High
10 AWG5.26 mm²30 A9.45 V (4.54%)198.5 V15.59 V (7.49%)1800.6 WDrop/Amp High
8 AWG8.37 mm²50 A5.94 V (2.86%)202.1 V9.8 V (4.71%)1131.5 WDrop/Amp High
6 AWG13.3 mm²65 A3.74 V (1.8%)204.3 V6.17 V (2.96%)712.1 WDrop/Amp High
4 AWG21.15 mm²85 A2.35 V (1.13%)205.6 V3.88 V (1.86%)447.8 WDrop/Amp High
3 AWG26.67 mm²100 A1.86 V (0.9%)206.1 V3.07 V (1.48%)355.1 WDrop/Amp High
2 AWG33.62 mm²115 A1.48 V (0.71%)206.5 V2.44 V (1.17%)281.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.17 V (0.56%)206.8 V1.93 V (0.93%)223.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.93 V (0.45%)207.1 V1.53 V (0.74%)177.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.74 V (0.35%)207.3 V1.22 V (0.58%)140.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.58 V (0.28%)207.4 V0.96 V (0.46%)111.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.46 V (0.22%)207.5 V0.76 V (0.37%)88.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.39 V (0.19%)207.6 V0.65 V (0.31%)74.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.33 V (0.16%)207.7 V0.54 V (0.26%)62.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.28 V (0.13%)207.7 V0.46 V (0.22%)53.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.25 V (0.12%)207.8 V0.4 V (0.19%)46.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.2 V (0.09%)207.8 V0.32 V (0.16%)37.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (0.08%)207.8 V0.27 V (0.13%)31.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.06%)207.9 V0.22 V (0.1%)24.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.05%)207.9 V0.16 V (0.08%)18.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 40 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 40 feet one-way at 208V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 1.48V (0.71%) and delivers 206.5V at the load.

What size aluminum wire is required for 110 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 1.53V (0.74%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.