🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 5.32V (2.56%)
Voltage at Load End202.9 VLoss: 5.13 V (977.0 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A104.56 V (50.27%)103.4 V172.47 V (82.92%)19921.0 WDrop/Amp High
12 AWG3.31 mm²20 A65.7 V (31.59%)142.3 V108.38 V (52.11%)12518.3 WDrop/Amp High
10 AWG5.26 mm²30 A41.35 V (19.88%)166.7 V68.2 V (32.79%)7877.5 WDrop/Amp High
8 AWG8.37 mm²50 A25.98 V (12.49%)182.0 V42.86 V (20.61%)4950.5 WDrop/Amp High
6 AWG13.3 mm²65 A16.35 V (7.86%)191.6 V26.97 V (12.97%)3115.5 WDrop/Amp High
4 AWG21.15 mm²85 A10.28 V (4.94%)197.7 V16.96 V (8.15%)1959.1 WDrop/Amp High
3 AWG26.67 mm²100 A8.15 V (3.92%)199.8 V13.45 V (6.47%)1553.6 WDrop/Amp High
2 AWG33.62 mm²115 A6.47 V (3.11%)201.5 V10.67 V (5.13%)1232.5 W~ ≤5%
1 AWG42.41 mm²130 A5.13 V (2.47%)202.9 V8.46 V (4.07%)977.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.07 V (1.95%)203.9 V6.71 V (3.22%)774.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.23 V (1.55%)204.8 V5.32 V (2.56%)614.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.56 V (1.23%)205.4 V4.22 V (2.03%)487.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.03 V (0.98%)206.0 V3.35 V (1.61%)386.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.72 V (0.83%)206.3 V2.83 V (1.36%)327.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.43 V (0.69%)206.6 V2.36 V (1.13%)272.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.23 V (0.59%)206.8 V2.02 V (0.97%)233.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.07 V (0.52%)206.9 V1.77 V (0.85%)204.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.86 V (0.41%)207.1 V1.42 V (0.68%)163.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.72 V (0.34%)207.3 V1.18 V (0.57%)136.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.57 V (0.28%)207.4 V0.94 V (0.45%)109.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.43 V (0.21%)207.6 V0.71 V (0.34%)81.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 175 feet one-way at 208V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.13V (2.47%) and delivers 202.9V at the load.

What size aluminum wire is required for 110 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 5.32V (2.56%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.