🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 800 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.74V (31.14%)
Voltage at Load End11.7 VLoss: 0.32 V (35.6 W)
Power & Breaker (125%)1.32 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 800 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A551.92 V (4599.35%)0.0 V910.41 V (7586.78%)60711.5 WDrop/Amp High
12 AWG3.31 mm²20 A346.83 V (2890.23%)0.0 V572.1 V (4767.53%)38151.0 WDrop/Amp High
10 AWG5.26 mm²30 A218.25 V (1818.76%)0.0 V360.01 V (3000.1%)24007.6 WDrop/Amp High
8 AWG8.37 mm²50 A137.16 V (1142.97%)0.0 V226.24 V (1885.37%)15087.2 WDrop/Amp High
6 AWG13.3 mm²65 A86.32 V (719.3%)0.0 V142.38 V (1186.5%)9494.7 WDrop/Amp High
4 AWG21.15 mm²85 A54.28 V (452.32%)0.0 V89.53 V (746.12%)5970.7 WDrop/Amp High
3 AWG26.67 mm²100 A43.04 V (358.7%)0.0 V71.0 V (591.7%)4734.9 WDrop/Amp High
2 AWG33.62 mm²115 A34.15 V (284.55%)0.0 V56.33 V (469.38%)3756.1 WDrop/Amp High
1 AWG42.41 mm²130 A27.07 V (225.58%)0.0 V44.65 V (372.09%)2977.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.46 V (178.85%)0.0 V35.4 V (295.02%)2360.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.03 V (141.88%)0.0 V28.08 V (234.03%)1872.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.5 V (112.54%)0.0 V22.28 V (185.63%)1485.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.71 V (89.24%)1.3 V17.66 V (147.21%)1178.0 WDrop/Amp High
250 kcmil126.7 mm²255 A9.06 V (75.51%)2.9 V14.95 V (124.55%)996.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.55 V (62.94%)4.4 V12.46 V (103.82%)830.8 WDrop/Amp High
350 kcmil177.3 mm²310 A6.47 V (53.96%)5.5 V10.68 V (89.0%)712.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.66 V (47.2%)6.3 V9.34 V (77.85%)623.0 WDrop/Amp High
500 kcmil253.4 mm²380 A4.53 V (37.75%)7.5 V7.47 V (62.28%)498.3 WDrop/Amp High
600 kcmil304.0 mm²420 A3.78 V (31.47%)8.2 V6.23 V (51.91%)415.4 WDrop/Amp High
750 kcmil380.0 mm²475 A3.02 V (25.18%)9.0 V4.98 V (41.53%)332.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.27 V (18.88%)9.7 V3.74 V (31.14%)249.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 800 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 800 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.7%) and delivers 11.7V at the load.

What size aluminum wire is required for 110 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.74V (31.14%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.