⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.73%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 6.47V (2.7%)
Voltage at Load End233.5 VLoss: 6.54 V (1246.2 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A477.98 V (199.16%)0.0 V788.44 V (328.52%)91067.2 WDrop/Amp High
12 AWG3.31 mm²20 A300.36 V (125.15%)0.0 V495.46 V (206.44%)57226.5 WDrop/Amp High
10 AWG5.26 mm²30 A189.01 V (78.75%)51.0 V311.78 V (129.91%)36011.4 WDrop/Amp High
8 AWG8.37 mm²50 A118.78 V (49.49%)121.2 V195.93 V (81.64%)22630.8 WDrop/Amp High
6 AWG13.3 mm²65 A74.75 V (31.15%)165.2 V123.31 V (51.38%)14242.1 WDrop/Amp High
4 AWG21.15 mm²85 A47.01 V (19.59%)193.0 V77.54 V (32.31%)8956.0 WDrop/Amp High
3 AWG26.67 mm²100 A37.28 V (15.53%)202.7 V61.49 V (25.62%)7102.4 WDrop/Amp High
2 AWG33.62 mm²115 A29.57 V (12.32%)210.4 V48.78 V (20.32%)5634.1 WDrop/Amp High
1 AWG42.41 mm²130 A23.44 V (9.77%)216.6 V38.67 V (16.11%)4466.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.59 V (7.74%)221.4 V30.66 V (12.77%)3541.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.74 V (6.14%)225.3 V24.32 V (10.13%)2809.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.7 V (4.87%)228.3 V19.29 V (8.04%)2228.2 W~ ≤5%
4/0 AWG107.2 mm²230 A9.27 V (3.86%)230.7 V15.3 V (6.37%)1767.0 W~ ≤5%
250 kcmil126.7 mm²255 A7.85 V (3.27%)232.2 V12.94 V (5.39%)1495.0 W~ ≤5%
300 kcmil152.0 mm²285 A6.54 V (2.73%)233.5 V10.79 V (4.5%)1246.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.61 V (2.34%)234.4 V9.25 V (3.85%)1068.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.9 V (2.04%)235.1 V8.09 V (3.37%)934.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.92 V (1.63%)236.1 V6.47 V (2.7%)747.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.27 V (1.36%)236.7 V5.39 V (2.25%)623.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.62 V (1.09%)237.4 V4.32 V (1.8%)498.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.96 V (0.82%)238.0 V3.24 V (1.35%)373.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 800 feet one-way at 240V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 6.54V (2.73%) and delivers 233.5V at the load.

What size aluminum wire is required for 110 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 6.47V (2.7%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.