175 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.34V (2.79%)
Voltage at Load End116.6 VLoss: 3.38 V (591.4 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A246.95 V (205.79%)0.0 V407.36 V (339.47%)43216.9 WDrop/Amp High
12 AWG3.31 mm²20 A155.19 V (129.32%)0.0 V255.98 V (213.32%)27157.5 WDrop/Amp High
10 AWG5.26 mm²30 A97.65 V (81.38%)22.3 V161.08 V (134.24%)17089.6 WDrop/Amp High
8 AWG8.37 mm²50 A61.37 V (51.14%)58.6 V101.23 V (84.36%)10739.7 WDrop/Amp High
6 AWG13.3 mm²65 A38.62 V (32.18%)81.4 V63.71 V (53.09%)6758.7 WDrop/Amp High
4 AWG21.15 mm²85 A24.29 V (20.24%)95.7 V40.06 V (33.38%)4250.2 WDrop/Amp High
3 AWG26.67 mm²100 A19.26 V (16.05%)100.7 V31.77 V (26.47%)3370.5 WDrop/Amp High
2 AWG33.62 mm²115 A15.28 V (12.73%)104.7 V25.2 V (21.0%)2673.7 WDrop/Amp High
1 AWG42.41 mm²130 A12.11 V (10.09%)107.9 V19.98 V (16.65%)2119.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.6 V (8.0%)110.4 V15.84 V (13.2%)1680.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.62 V (6.35%)112.4 V12.57 V (10.47%)1333.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.04 V (5.04%)114.0 V9.97 V (8.31%)1057.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.79 V (3.99%)115.2 V7.9 V (6.59%)838.5 W~ ≤5%
250 kcmil126.7 mm²255 A4.05 V (3.38%)115.9 V6.69 V (5.57%)709.5 W~ ≤5%
300 kcmil152.0 mm²285 A3.38 V (2.82%)116.6 V5.57 V (4.65%)591.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.9 V (2.41%)117.1 V4.78 V (3.98%)507.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.53 V (2.11%)117.5 V4.18 V (3.48%)443.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.03 V (1.69%)118.0 V3.34 V (2.79%)354.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.69 V (1.41%)118.3 V2.79 V (2.32%)295.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.35 V (1.13%)118.6 V2.23 V (1.86%)236.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.01 V (0.84%)119.0 V1.67 V (1.39%)177.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 225 feet one-way at 120V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.38V (2.82%) and delivers 116.6V at the load.

What size aluminum wire is required for 175 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.34V (2.79%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.