🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.11%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.21V (1.29%)
Voltage at Load End474.7 VLoss: 5.34 V (2079.2 W)
Power & Breaker (125%)187.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.97 V (57.29%)205.0 V453.58 V (94.5%)107160.4 WDrop/Amp High
12 AWG3.31 mm²20 A172.79 V (36.0%)307.2 V285.03 V (59.38%)67339.4 WDrop/Amp High
10 AWG5.26 mm²30 A108.73 V (22.65%)371.3 V179.36 V (37.37%)42375.2 WDrop/Amp High
8 AWG8.37 mm²50 A68.33 V (14.24%)411.7 V112.72 V (23.48%)26630.1 WDrop/Amp High
6 AWG13.3 mm²65 A43.0 V (8.96%)437.0 V70.94 V (14.78%)16758.9 WDrop/Amp High
4 AWG21.15 mm²85 A27.04 V (5.63%)453.0 V44.61 V (9.29%)10538.7 WDrop/Amp High
3 AWG26.67 mm²100 A21.45 V (4.47%)458.6 V35.37 V (7.37%)8357.5 WDrop/Amp High
2 AWG33.62 mm²115 A17.01 V (3.54%)463.0 V28.06 V (5.85%)6629.8 WDrop/Amp High
1 AWG42.41 mm²130 A13.49 V (2.81%)466.5 V22.25 V (4.63%)5255.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.69 V (2.23%)469.3 V17.64 V (3.67%)4167.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.48 V (1.77%)471.5 V13.99 V (2.91%)3305.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.73 V (1.4%)473.3 V11.1 V (2.31%)2622.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.34 V (1.11%)474.7 V8.8 V (1.83%)2079.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.51 V (0.94%)475.5 V7.45 V (1.55%)1759.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.76 V (0.78%)476.2 V6.21 V (1.29%)1466.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.23 V (0.67%)476.8 V5.32 V (1.11%)1257.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.82 V (0.59%)477.2 V4.65 V (0.97%)1099.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.26 V (0.47%)477.7 V3.72 V (0.78%)879.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.88 V (0.39%)478.1 V3.1 V (0.65%)733.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.51 V (0.31%)478.5 V2.48 V (0.52%)586.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.24%)478.9 V1.86 V (0.39%)439.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 225 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.34V (1.11%) and delivers 474.7V at the load.

What size aluminum wire is required for 225 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.21V (1.29%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.