🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.52V (2.3%)
Voltage at Load End233.3 VLoss: 6.69 V (2895.8 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A814.74 V (339.47%)0.0 V1343.93 V (559.97%)352791.3 WDrop/Amp High
12 AWG3.31 mm²20 A511.98 V (213.32%)0.0 V844.53 V (351.89%)221693.7 WDrop/Amp High
10 AWG5.26 mm²30 A322.18 V (134.24%)0.0 V531.44 V (221.43%)139506.8 WDrop/Amp High
8 AWG8.37 mm²50 A202.47 V (84.36%)37.5 V333.98 V (139.16%)87671.0 WDrop/Amp High
6 AWG13.3 mm²65 A127.42 V (53.09%)112.6 V210.18 V (87.57%)55173.4 WDrop/Amp High
4 AWG21.15 mm²85 A80.13 V (33.39%)159.9 V132.17 V (55.07%)34695.3 WDrop/Amp High
3 AWG26.67 mm²100 A63.54 V (26.48%)176.5 V104.81 V (43.67%)27514.3 WDrop/Amp High
2 AWG33.62 mm²115 A50.41 V (21.0%)189.6 V83.15 V (34.64%)21826.5 WDrop/Amp High
1 AWG42.41 mm²130 A39.96 V (16.65%)200.0 V65.91 V (27.46%)17302.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.68 V (13.2%)208.3 V52.26 V (21.77%)13718.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.13 V (10.47%)214.9 V41.46 V (17.27%)10882.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.93 V (8.31%)220.1 V32.88 V (13.7%)8632.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.81 V (6.59%)224.2 V26.08 V (10.87%)6845.2 WDrop/Amp High
250 kcmil126.7 mm²255 A13.38 V (5.57%)226.6 V22.06 V (9.19%)5791.7 WDrop/Amp High
300 kcmil152.0 mm²285 A11.15 V (4.65%)228.9 V18.39 V (7.66%)4827.7 W~ ≤5%
350 kcmil177.3 mm²310 A9.56 V (3.98%)230.4 V15.77 V (6.57%)4138.8 W~ ≤5%
400 kcmil202.7 mm²335 A8.36 V (3.48%)231.6 V13.79 V (5.75%)3620.2 W~ ≤5%
500 kcmil253.4 mm²380 A6.69 V (2.79%)233.3 V11.03 V (4.6%)2895.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.57 V (2.32%)234.4 V9.2 V (3.83%)2413.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.46 V (1.86%)235.5 V7.36 V (3.07%)1931.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.34 V (1.39%)236.7 V5.52 V (2.3%)1448.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 600 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 250 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.52V (2.3%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.