🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 13.49V (2.81%)
Voltage at Load End467.7 VLoss: 12.26 V (5839.9 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1493.68 V (311.18%)0.0 V2463.88 V (513.31%)711462.5 WDrop/Amp High
12 AWG3.31 mm²20 A938.63 V (195.55%)0.0 V1548.3 V (322.56%)447082.2 WDrop/Amp High
10 AWG5.26 mm²30 A590.66 V (123.05%)0.0 V974.31 V (202.98%)281338.8 WDrop/Amp High
8 AWG8.37 mm²50 A371.19 V (77.33%)108.8 V612.29 V (127.56%)176803.1 WDrop/Amp High
6 AWG13.3 mm²65 A233.6 V (48.67%)246.4 V385.33 V (80.28%)111266.3 WDrop/Amp High
4 AWG21.15 mm²85 A146.9 V (30.6%)333.1 V242.31 V (50.48%)69968.9 WDrop/Amp High
3 AWG26.67 mm²100 A116.49 V (24.27%)363.5 V192.16 V (40.03%)55487.1 WDrop/Amp High
2 AWG33.62 mm²115 A92.41 V (19.25%)387.6 V152.44 V (31.76%)44016.7 WDrop/Amp High
1 AWG42.41 mm²130 A73.26 V (15.26%)406.7 V120.84 V (25.18%)34893.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A58.08 V (12.1%)421.9 V95.81 V (19.96%)27665.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A46.08 V (9.6%)433.9 V76.0 V (15.83%)21946.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A36.55 V (7.61%)443.5 V60.29 V (12.56%)17407.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A28.98 V (6.04%)451.0 V47.81 V (9.96%)13804.5 WDrop/Amp High
250 kcmil126.7 mm²255 A24.52 V (5.11%)455.5 V40.45 V (8.43%)11679.9 WDrop/Amp High
300 kcmil152.0 mm²285 A20.44 V (4.26%)459.6 V33.72 V (7.02%)9735.8 W~ ≤5%
350 kcmil177.3 mm²310 A17.52 V (3.65%)462.5 V28.91 V (6.02%)8346.5 W~ ≤5%
400 kcmil202.7 mm²335 A15.33 V (3.19%)464.7 V25.28 V (5.27%)7300.7 W~ ≤5%
500 kcmil253.4 mm²380 A12.26 V (2.55%)467.7 V20.22 V (4.21%)5839.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A10.22 V (2.13%)469.8 V16.86 V (3.51%)4867.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A8.18 V (1.7%)471.8 V13.49 V (2.81%)3894.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A6.13 V (1.28%)473.9 V10.11 V (2.11%)2920.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 1000 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 12.26V (2.55%) and delivers 467.7V at the load.

What size aluminum wire is required for 275 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 13.49V (2.81%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.