🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.35%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 0.46V (0.38%)
Voltage at Load End119.6 VLoss: 0.42 V (136.0 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.77 V (33.97%)79.2 V67.25 V (56.04%)13249.3 WDrop/Amp High
12 AWG3.31 mm²20 A25.62 V (21.35%)94.4 V42.26 V (35.21%)8325.8 WDrop/Amp High
10 AWG5.26 mm²30 A16.12 V (13.43%)103.9 V26.59 V (22.16%)5239.3 WDrop/Amp High
8 AWG8.37 mm²50 A10.13 V (8.44%)109.9 V16.71 V (13.93%)3292.5 WDrop/Amp High
6 AWG13.3 mm²65 A6.38 V (5.31%)113.6 V10.52 V (8.76%)2072.1 WDrop/Amp High
4 AWG21.15 mm²85 A4.01 V (3.34%)116.0 V6.61 V (5.51%)1303.0 WDrop/Amp High
3 AWG26.67 mm²100 A3.18 V (2.65%)116.8 V5.24 V (4.37%)1033.3 WDrop/Amp High
2 AWG33.62 mm²115 A2.52 V (2.1%)117.5 V4.16 V (3.47%)819.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.0 V (1.67%)118.0 V3.3 V (2.75%)649.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.59 V (1.32%)118.4 V2.61 V (2.18%)515.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.26 V (1.05%)118.7 V2.07 V (1.73%)408.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.0 V (0.83%)119.0 V1.65 V (1.37%)324.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.79 V (0.66%)119.2 V1.3 V (1.09%)257.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.67 V (0.56%)119.3 V1.1 V (0.92%)217.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.56 V (0.46%)119.4 V0.92 V (0.77%)181.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.48 V (0.4%)119.5 V0.79 V (0.66%)155.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.42 V (0.35%)119.6 V0.69 V (0.58%)136.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.33 V (0.28%)119.7 V0.55 V (0.46%)108.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.28 V (0.23%)119.7 V0.46 V (0.38%)90.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (0.19%)119.8 V0.37 V (0.31%)72.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.14%)119.8 V0.28 V (0.23%)54.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 20 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 0.42V (0.35%) and delivers 119.6V at the load.

What size aluminum wire is required for 325 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 0.46V (0.38%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.