⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 60 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.05%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.38V (1.15%)
Voltage at Load End118.7 VLoss: 1.25 V (407.9 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 60 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.3 V (101.92%)0.0 V201.74 V (168.12%)39747.8 WDrop/Amp High
12 AWG3.31 mm²20 A76.85 V (64.04%)43.1 V126.77 V (105.64%)24977.5 WDrop/Amp High
10 AWG5.26 mm²30 A48.36 V (40.3%)71.6 V79.78 V (66.48%)15717.8 WDrop/Amp High
8 AWG8.37 mm²50 A30.39 V (25.33%)89.6 V50.13 V (41.78%)9877.6 WDrop/Amp High
6 AWG13.3 mm²65 A19.13 V (15.94%)100.9 V31.55 V (26.29%)6216.2 WDrop/Amp High
4 AWG21.15 mm²85 A12.03 V (10.02%)108.0 V19.84 V (16.53%)3909.0 WDrop/Amp High
3 AWG26.67 mm²100 A9.54 V (7.95%)110.5 V15.73 V (13.11%)3099.9 WDrop/Amp High
2 AWG33.62 mm²115 A7.57 V (6.31%)112.4 V12.48 V (10.4%)2459.1 WDrop/Amp High
1 AWG42.41 mm²130 A6.0 V (5.0%)114.0 V9.89 V (8.25%)1949.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.76 V (3.96%)115.2 V7.84 V (6.54%)1545.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.77 V (3.14%)116.2 V6.22 V (5.19%)1226.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.99 V (2.49%)117.0 V4.94 V (4.11%)972.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.37 V (1.98%)117.6 V3.91 V (3.26%)771.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.01 V (1.67%)118.0 V3.31 V (2.76%)652.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.67 V (1.39%)118.3 V2.76 V (2.3%)543.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.43 V (1.2%)118.6 V2.37 V (1.97%)466.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.25 V (1.05%)118.7 V2.07 V (1.73%)407.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.0 V (0.84%)119.0 V1.66 V (1.38%)326.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.84 V (0.7%)119.2 V1.38 V (1.15%)272.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.67 V (0.56%)119.3 V1.1 V (0.92%)217.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.42%)119.5 V0.83 V (0.69%)163.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 60 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 60 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.25V (1.05%) and delivers 118.7V at the load.

What size aluminum wire is required for 325 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.38V (1.15%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.