🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.31%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.73V (1.44%)
Voltage at Load End118.4 VLoss: 1.57 V (509.8 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.88 V (127.4%)0.0 V252.17 V (210.15%)49684.8 WDrop/Amp High
12 AWG3.31 mm²20 A96.07 V (80.06%)23.9 V158.47 V (132.06%)31221.9 WDrop/Amp High
10 AWG5.26 mm²30 A60.45 V (50.38%)59.5 V99.72 V (83.1%)19647.2 WDrop/Amp High
8 AWG8.37 mm²50 A37.99 V (31.66%)82.0 V62.67 V (52.22%)12347.0 WDrop/Amp High
6 AWG13.3 mm²65 A23.91 V (19.92%)96.1 V39.44 V (32.86%)7770.3 WDrop/Amp High
4 AWG21.15 mm²85 A15.03 V (12.53%)105.0 V24.8 V (20.67%)4886.3 WDrop/Amp High
3 AWG26.67 mm²100 A11.92 V (9.94%)108.1 V19.67 V (16.39%)3874.9 WDrop/Amp High
2 AWG33.62 mm²115 A9.46 V (7.88%)110.5 V15.6 V (13.0%)3073.9 WDrop/Amp High
1 AWG42.41 mm²130 A7.5 V (6.25%)112.5 V12.37 V (10.31%)2436.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.94 V (4.95%)114.1 V9.81 V (8.17%)1932.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.72 V (3.93%)115.3 V7.78 V (6.48%)1532.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.74 V (3.12%)116.3 V6.17 V (5.14%)1215.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.97 V (2.47%)117.0 V4.89 V (4.08%)964.0 WDrop/Amp High
250 kcmil126.7 mm²255 A2.51 V (2.09%)117.5 V4.14 V (3.45%)815.7 WDrop/Amp High
300 kcmil152.0 mm²285 A2.09 V (1.74%)117.9 V3.45 V (2.88%)679.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.79 V (1.49%)118.2 V2.96 V (2.47%)582.9 WDrop/Amp High
400 kcmil202.7 mm²335 A1.57 V (1.31%)118.4 V2.59 V (2.16%)509.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.25 V (1.05%)118.7 V2.07 V (1.72%)407.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.05 V (0.87%)119.0 V1.73 V (1.44%)339.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.84 V (0.7%)119.2 V1.38 V (1.15%)272.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.63 V (0.52%)119.4 V1.04 V (0.86%)204.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 75 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.57V (1.31%) and delivers 118.4V at the load.

What size aluminum wire is required for 325 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.73V (1.44%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.