⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.87%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.15V (0.96%)
Voltage at Load End119.0 VLoss: 1.05 V (339.9 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A101.92 V (84.93%)18.1 V168.12 V (140.1%)33123.2 WDrop/Amp High
12 AWG3.31 mm²20 A64.04 V (53.37%)56.0 V105.64 V (88.04%)20814.6 WDrop/Amp High
10 AWG5.26 mm²30 A40.3 V (33.58%)79.7 V66.48 V (55.4%)13098.1 WDrop/Amp High
8 AWG8.37 mm²50 A25.33 V (21.11%)94.7 V41.78 V (34.81%)8231.3 WDrop/Amp High
6 AWG13.3 mm²65 A15.94 V (13.28%)104.1 V26.29 V (21.91%)5180.2 WDrop/Amp High
4 AWG21.15 mm²85 A10.02 V (8.35%)110.0 V16.53 V (13.78%)3257.5 WDrop/Amp High
3 AWG26.67 mm²100 A7.95 V (6.62%)112.1 V13.11 V (10.93%)2583.3 WDrop/Amp High
2 AWG33.62 mm²115 A6.31 V (5.25%)113.7 V10.4 V (8.67%)2049.3 WDrop/Amp High
1 AWG42.41 mm²130 A5.0 V (4.17%)115.0 V8.25 V (6.87%)1624.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.96 V (3.3%)116.0 V6.54 V (5.45%)1288.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.14 V (2.62%)116.9 V5.19 V (4.32%)1021.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.49 V (2.08%)117.5 V4.11 V (3.43%)810.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.98 V (1.65%)118.0 V3.26 V (2.72%)642.7 WDrop/Amp High
250 kcmil126.7 mm²255 A1.67 V (1.39%)118.3 V2.76 V (2.3%)543.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.39 V (1.16%)118.6 V2.3 V (1.92%)453.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.2 V (1.0%)118.8 V1.97 V (1.64%)388.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.05 V (0.87%)119.0 V1.73 V (1.44%)339.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.84 V (0.7%)119.2 V1.38 V (1.15%)271.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.7 V (0.58%)119.3 V1.15 V (0.96%)226.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.56 V (0.46%)119.4 V0.92 V (0.77%)181.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.42 V (0.35%)119.6 V0.69 V (0.58%)136.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 50 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.05V (0.87%) and delivers 119.0V at the load.

What size aluminum wire is required for 325 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.15V (0.96%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.