325 Amp Wire Size at 100 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.74%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 2.3V (1.92%)
Voltage at Load End117.9 VLoss: 2.09 V (679.8 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 100 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A203.83 V (169.86%)0.0 V336.23 V (280.19%)66246.4 WDrop/Amp High
12 AWG3.31 mm²20 A128.09 V (106.74%)0.0 V211.29 V (176.07%)41629.1 WDrop/Amp High
10 AWG5.26 mm²30 A80.6 V (67.17%)39.4 V132.96 V (110.8%)26196.3 WDrop/Amp High
8 AWG8.37 mm²50 A50.65 V (42.21%)69.3 V83.56 V (69.63%)16462.7 WDrop/Amp High
6 AWG13.3 mm²65 A31.88 V (26.56%)88.1 V52.58 V (43.82%)10360.3 WDrop/Amp High
4 AWG21.15 mm²85 A20.05 V (16.71%)100.0 V33.07 V (27.56%)6515.0 WDrop/Amp High
3 AWG26.67 mm²100 A15.9 V (13.25%)104.1 V26.22 V (21.85%)5166.6 WDrop/Amp High
2 AWG33.62 mm²115 A12.61 V (10.51%)107.4 V20.8 V (17.34%)4098.5 WDrop/Amp High
1 AWG42.41 mm²130 A10.0 V (8.33%)110.0 V16.49 V (13.74%)3249.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.93 V (6.61%)112.1 V13.07 V (10.9%)2576.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.29 V (5.24%)113.7 V10.37 V (8.64%)2043.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.99 V (4.16%)115.0 V8.23 V (6.86%)1620.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.96 V (3.3%)116.0 V6.52 V (5.44%)1285.4 WDrop/Amp High
250 kcmil126.7 mm²255 A3.35 V (2.79%)116.7 V5.52 V (4.6%)1087.5 WDrop/Amp High
300 kcmil152.0 mm²285 A2.79 V (2.32%)117.2 V4.6 V (3.83%)906.5 WDrop/Amp High
350 kcmil177.3 mm²310 A2.39 V (1.99%)117.6 V3.94 V (3.29%)777.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.09 V (1.74%)117.9 V3.45 V (2.88%)679.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.67 V (1.39%)118.3 V2.76 V (2.3%)543.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.39 V (1.16%)118.6 V2.3 V (1.92%)453.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.12 V (0.93%)118.9 V1.84 V (1.53%)362.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.84 V (0.7%)119.2 V1.38 V (1.15%)271.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 100 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 100 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 2.09V (1.74%) and delivers 117.9V at the load.

What size aluminum wire is required for 325 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 2.3V (1.92%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.