⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.39%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.84V (1.53%)
Voltage at Load End118.3 VLoss: 1.67 V (543.8 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A163.07 V (135.89%)0.0 V268.99 V (224.15%)52997.1 WDrop/Amp High
12 AWG3.31 mm²20 A102.47 V (85.39%)17.5 V169.03 V (140.86%)33303.3 WDrop/Amp High
10 AWG5.26 mm²30 A64.48 V (53.74%)55.5 V106.37 V (88.64%)20957.0 WDrop/Amp High
8 AWG8.37 mm²50 A40.52 V (33.77%)79.5 V66.84 V (55.7%)13170.1 WDrop/Amp High
6 AWG13.3 mm²65 A25.5 V (21.25%)94.5 V42.07 V (35.06%)8288.3 WDrop/Amp High
4 AWG21.15 mm²85 A16.04 V (13.36%)104.0 V26.45 V (22.04%)5212.0 WDrop/Amp High
3 AWG26.67 mm²100 A12.72 V (10.6%)107.3 V20.98 V (17.48%)4133.3 WDrop/Amp High
2 AWG33.62 mm²115 A10.09 V (8.41%)109.9 V16.64 V (13.87%)3278.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.0 V (6.66%)112.0 V13.19 V (10.99%)2599.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.34 V (5.28%)113.7 V10.46 V (8.72%)2060.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.03 V (4.19%)115.0 V8.3 V (6.91%)1634.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.99 V (3.32%)116.0 V6.58 V (5.48%)1296.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.16 V (2.64%)116.8 V5.22 V (4.35%)1028.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.68 V (2.23%)117.3 V4.42 V (3.68%)870.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.23 V (1.86%)117.8 V3.68 V (3.07%)725.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.91 V (1.59%)118.1 V3.16 V (2.63%)621.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.67 V (1.39%)118.3 V2.76 V (2.3%)543.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.34 V (1.12%)118.7 V2.21 V (1.84%)435.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.12 V (0.93%)118.9 V1.84 V (1.53%)362.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.89 V (0.74%)119.1 V1.47 V (1.23%)290.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.67 V (0.56%)119.3 V1.1 V (0.92%)217.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 80 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.67V (1.39%) and delivers 118.3V at the load.

What size aluminum wire is required for 325 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.84V (1.53%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.