🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.22V (2.68%)
Voltage at Load End117.1 VLoss: 2.93 V (951.6 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A356.71 V (297.26%)0.0 V588.41 V (490.34%)115931.2 WDrop/Amp High
12 AWG3.31 mm²20 A224.16 V (186.8%)0.0 V369.75 V (308.13%)72851.0 WDrop/Amp High
10 AWG5.26 mm²30 A141.06 V (117.55%)0.0 V232.68 V (193.9%)45843.5 WDrop/Amp High
8 AWG8.37 mm²50 A88.65 V (73.87%)31.4 V146.22 V (121.85%)28809.7 WDrop/Amp High
6 AWG13.3 mm²65 A55.79 V (46.49%)64.2 V92.02 V (76.68%)18130.6 WDrop/Amp High
4 AWG21.15 mm²85 A35.08 V (29.23%)84.9 V57.87 V (48.22%)11401.3 WDrop/Amp High
3 AWG26.67 mm²100 A27.82 V (23.18%)92.2 V45.89 V (38.24%)9041.5 WDrop/Amp High
2 AWG33.62 mm²115 A22.07 V (18.39%)97.9 V36.4 V (30.34%)7172.4 WDrop/Amp High
1 AWG42.41 mm²130 A17.49 V (14.58%)102.5 V28.86 V (24.05%)5685.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.87 V (11.56%)106.1 V22.88 V (19.07%)4508.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.0 V (9.17%)109.0 V18.15 V (15.13%)3576.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.73 V (7.27%)111.3 V14.4 V (12.0%)2836.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.92 V (5.77%)113.1 V11.42 V (9.51%)2249.4 WDrop/Amp High
250 kcmil126.7 mm²255 A5.86 V (4.88%)114.1 V9.66 V (8.05%)1903.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.88 V (4.07%)115.1 V8.05 V (6.71%)1586.4 WDrop/Amp High
350 kcmil177.3 mm²310 A4.18 V (3.49%)115.8 V6.9 V (5.75%)1360.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.66 V (3.05%)116.3 V6.04 V (5.03%)1189.6 W~ ≤5%
500 kcmil253.4 mm²380 A2.93 V (2.44%)117.1 V4.83 V (4.02%)951.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.44 V (2.03%)117.6 V4.03 V (3.35%)793.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.95 V (1.63%)118.0 V3.22 V (2.68%)634.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.46 V (1.22%)118.5 V2.42 V (2.01%)475.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 175 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.93V (2.44%) and delivers 117.1V at the load.

What size aluminum wire is required for 325 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.22V (2.68%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.