🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.61%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 3.45V (2.88%)
Voltage at Load End116.9 VLoss: 3.14 V (1019.7 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A305.75 V (254.79%)0.0 V504.35 V (420.29%)99369.6 WDrop/Amp High
12 AWG3.31 mm²20 A192.13 V (160.11%)0.0 V316.93 V (264.11%)62443.7 WDrop/Amp High
10 AWG5.26 mm²30 A120.91 V (100.75%)0.0 V199.44 V (166.2%)39294.4 WDrop/Amp High
8 AWG8.37 mm²50 A75.98 V (63.32%)44.0 V125.33 V (104.44%)24694.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.82 V (39.85%)72.2 V78.88 V (65.73%)15540.5 WDrop/Amp High
4 AWG21.15 mm²85 A30.07 V (25.06%)89.9 V49.6 V (41.33%)9772.5 WDrop/Amp High
3 AWG26.67 mm²100 A23.85 V (19.87%)96.2 V39.33 V (32.78%)7749.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.92 V (15.76%)101.1 V31.2 V (26.0%)6147.8 WDrop/Amp High
1 AWG42.41 mm²130 A15.0 V (12.5%)105.0 V24.74 V (20.61%)4873.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.89 V (9.91%)108.1 V19.61 V (16.34%)3864.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.43 V (7.86%)110.6 V15.56 V (12.96%)3065.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.48 V (6.23%)112.5 V12.34 V (10.28%)2431.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.93 V (4.94%)114.1 V9.79 V (8.15%)1928.1 WDrop/Amp High
250 kcmil126.7 mm²255 A5.02 V (4.18%)115.0 V8.28 V (6.9%)1631.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.18 V (3.49%)115.8 V6.9 V (5.75%)1359.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.59 V (2.99%)116.4 V5.92 V (4.93%)1165.8 WDrop/Amp High
400 kcmil202.7 mm²335 A3.14 V (2.61%)116.9 V5.18 V (4.31%)1019.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.51 V (2.09%)117.5 V4.14 V (3.45%)815.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.09 V (1.74%)117.9 V3.45 V (2.88%)679.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.67 V (1.39%)118.3 V2.76 V (2.3%)543.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.26 V (1.05%)118.7 V2.07 V (1.73%)407.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 150 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 3.14V (2.61%) and delivers 116.9V at the load.

What size aluminum wire is required for 325 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 3.45V (2.88%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.