🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.8V (31.63%)
Voltage at Load End11.7 VLoss: 0.33 V (106.8 W)
Power & Breaker (125%)3.9 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A560.55 V (4671.22%)0.0 V924.64 V (7705.33%)182177.5 WDrop/Amp High
12 AWG3.31 mm²20 A352.25 V (2935.39%)0.0 V581.04 V (4842.02%)114480.1 WDrop/Amp High
10 AWG5.26 mm²30 A221.66 V (1847.17%)0.0 V365.64 V (3046.97%)72039.8 WDrop/Amp High
8 AWG8.37 mm²50 A139.3 V (1160.83%)0.0 V229.78 V (1914.82%)45272.3 WDrop/Amp High
6 AWG13.3 mm²65 A87.66 V (730.54%)0.0 V144.61 V (1205.04%)28490.9 WDrop/Amp High
4 AWG21.15 mm²85 A55.13 V (459.39%)0.0 V90.93 V (757.78%)17916.3 WDrop/Amp High
3 AWG26.67 mm²100 A43.72 V (364.31%)0.0 V72.11 V (600.94%)14208.1 WDrop/Amp High
2 AWG33.62 mm²115 A34.68 V (289.0%)0.0 V57.21 V (476.71%)11270.9 WDrop/Amp High
1 AWG42.41 mm²130 A27.49 V (229.1%)0.0 V45.35 V (377.91%)8934.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.8 V (181.64%)0.0 V35.96 V (299.63%)7084.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.29 V (144.09%)0.0 V28.52 V (237.68%)5619.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.72 V (114.29%)0.0 V22.62 V (188.53%)4457.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.88 V (90.64%)1.1 V17.94 V (149.51%)3534.8 WDrop/Amp High
250 kcmil126.7 mm²255 A9.2 V (76.69%)2.8 V15.18 V (126.5%)2990.8 WDrop/Amp High
300 kcmil152.0 mm²285 A7.67 V (63.92%)4.3 V12.65 V (105.44%)2493.0 WDrop/Amp High
350 kcmil177.3 mm²310 A6.58 V (54.8%)5.4 V10.85 V (90.4%)2137.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.75 V (47.93%)6.2 V9.49 V (79.07%)1869.4 WDrop/Amp High
500 kcmil253.4 mm²380 A4.6 V (38.34%)7.4 V7.59 V (63.25%)1495.4 WDrop/Amp High
600 kcmil304.0 mm²420 A3.84 V (31.96%)8.2 V6.33 V (52.72%)1246.5 WDrop/Amp High
750 kcmil380.0 mm²475 A3.07 V (25.57%)8.9 V5.06 V (42.18%)997.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.3 V (19.18%)9.7 V3.8 V (31.63%)747.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 275 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.74%) and delivers 11.7V at the load.

What size aluminum wire is required for 325 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.8V (31.63%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.