🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 100 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.3V (2.48%)
Voltage at Load End11.7 VLoss: 0.3 V (10.5 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 100 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.95 V (182.93%)0.0 V36.21 V (301.75%)768.3 WDrop/Amp High
12 AWG3.31 mm²20 A13.79 V (114.95%)0.0 V22.75 V (189.62%)482.8 WDrop/Amp High
10 AWG5.26 mm²30 A8.68 V (72.34%)3.3 V14.32 V (119.32%)303.8 WDrop/Amp High
8 AWG8.37 mm²50 A5.46 V (45.46%)6.5 V9.0 V (74.99%)190.9 WDrop/Amp High
6 AWG13.3 mm²65 A3.43 V (28.61%)8.6 V5.66 V (47.19%)120.2 WDrop/Amp High
4 AWG21.15 mm²85 A2.16 V (17.99%)9.8 V3.56 V (29.68%)75.6 WDrop/Amp High
3 AWG26.67 mm²100 A1.71 V (14.27%)10.3 V2.82 V (23.53%)59.9 WDrop/Amp High
2 AWG33.62 mm²115 A1.36 V (11.32%)10.6 V2.24 V (18.67%)47.5 WDrop/Amp High
1 AWG42.41 mm²130 A1.08 V (8.97%)10.9 V1.78 V (14.8%)37.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.85 V (7.11%)11.1 V1.41 V (11.73%)29.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.68 V (5.64%)11.3 V1.12 V (9.31%)23.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.54 V (4.48%)11.5 V0.89 V (7.38%)18.8 W~ ≤5%
4/0 AWG107.2 mm²230 A0.43 V (3.55%)11.6 V0.7 V (5.85%)14.9 W~ ≤5%
250 kcmil126.7 mm²255 A0.36 V (3.0%)11.6 V0.59 V (4.95%)12.6 W~ ≤5%
300 kcmil152.0 mm²285 A0.3 V (2.5%)11.7 V0.5 V (4.13%)10.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (2.15%)11.7 V0.42 V (3.54%)9.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (1.88%)11.8 V0.37 V (3.1%)7.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.18 V (1.5%)11.8 V0.3 V (2.48%)6.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (1.25%)11.8 V0.25 V (2.06%)5.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (1.0%)11.9 V0.2 V (1.65%)4.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.75%)11.9 V0.15 V (1.24%)3.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 100 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 100 feet one-way at 12V (DC), you need 300 kcmil copper wire. This produces a voltage drop of 0.3V (2.5%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.3V (2.48%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.