⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 60 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 0.36V (2.97%)
Voltage at Load End11.7 VLoss: 0.32 V (11.3 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 60 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.17 V (109.76%)0.0 V21.73 V (181.05%)461.0 WDrop/Amp High
12 AWG3.31 mm²20 A8.28 V (68.97%)3.7 V13.65 V (113.77%)289.7 WDrop/Amp High
10 AWG5.26 mm²30 A5.21 V (43.4%)6.8 V8.59 V (71.59%)182.3 WDrop/Amp High
8 AWG8.37 mm²50 A3.27 V (27.28%)8.7 V5.4 V (44.99%)114.6 WDrop/Amp High
6 AWG13.3 mm²65 A2.06 V (17.17%)9.9 V3.4 V (28.31%)72.1 WDrop/Amp High
4 AWG21.15 mm²85 A1.3 V (10.79%)10.7 V2.14 V (17.81%)45.3 WDrop/Amp High
3 AWG26.67 mm²100 A1.03 V (8.56%)11.0 V1.69 V (14.12%)36.0 WDrop/Amp High
2 AWG33.62 mm²115 A0.81 V (6.79%)11.2 V1.34 V (11.2%)28.5 WDrop/Amp High
1 AWG42.41 mm²130 A0.65 V (5.38%)11.4 V1.07 V (8.88%)22.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.51 V (4.27%)11.5 V0.84 V (7.04%)17.9 W~ ≤5%
2/0 AWG67.43 mm²175 A0.41 V (3.39%)11.6 V0.67 V (5.58%)14.2 W~ ≤5%
3/0 AWG85.01 mm²200 A0.32 V (2.69%)11.7 V0.53 V (4.43%)11.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.26 V (2.13%)11.7 V0.42 V (3.51%)8.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.22 V (1.8%)11.8 V0.36 V (2.97%)7.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.18 V (1.5%)11.8 V0.3 V (2.48%)6.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.15 V (1.29%)11.8 V0.25 V (2.12%)5.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (1.13%)11.9 V0.22 V (1.86%)4.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.9%)11.9 V0.18 V (1.49%)3.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.75%)11.9 V0.15 V (1.24%)3.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.6%)11.9 V0.12 V (0.99%)2.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.45%)11.9 V0.09 V (0.74%)1.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 60 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 60 feet one-way at 12V (DC), you need 3/0 AWG copper wire. This produces a voltage drop of 0.32V (2.69%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 0.36V (2.97%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.