⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.85%
Aluminum Wire (≤3% Drop)1 AWGDrop: 0.36V (2.96%)
Voltage at Load End11.7 VLoss: 0.34 V (12.0 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.39 V (36.59%)7.6 V7.24 V (60.35%)153.7 WDrop/Amp High
12 AWG3.31 mm²20 A2.76 V (22.99%)9.2 V4.55 V (37.92%)96.6 WDrop/Amp High
10 AWG5.26 mm²30 A1.74 V (14.47%)10.3 V2.86 V (23.86%)60.8 WDrop/Amp High
8 AWG8.37 mm²50 A1.09 V (9.09%)10.9 V1.8 V (15.0%)38.2 WDrop/Amp High
6 AWG13.3 mm²65 A0.69 V (5.72%)11.3 V1.13 V (9.44%)24.0 WDrop/Amp High
4 AWG21.15 mm²85 A0.43 V (3.6%)11.6 V0.71 V (5.94%)15.1 W~ ≤5%
3 AWG26.67 mm²100 A0.34 V (2.85%)11.7 V0.56 V (4.71%)12.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.27 V (2.26%)11.7 V0.45 V (3.73%)9.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.22 V (1.79%)11.8 V0.36 V (2.96%)7.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.17 V (1.42%)11.8 V0.28 V (2.35%)6.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.14 V (1.13%)11.9 V0.22 V (1.86%)4.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.11 V (0.9%)11.9 V0.18 V (1.48%)3.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.09 V (0.71%)11.9 V0.14 V (1.17%)3.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.07 V (0.6%)11.9 V0.12 V (0.99%)2.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.06 V (0.5%)11.9 V0.1 V (0.83%)2.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.05 V (0.43%)11.9 V0.08 V (0.71%)1.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.05 V (0.38%)12.0 V0.07 V (0.62%)1.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.3%)12.0 V0.06 V (0.5%)1.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.25%)12.0 V0.05 V (0.41%)1.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.2%)12.0 V0.04 V (0.33%)0.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.15%)12.0 V0.03 V (0.25%)0.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 20 feet one-way at 12V (DC), you need 3 AWG copper wire. This produces a voltage drop of 0.34V (2.85%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 0.36V (2.96%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.