🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 0.34V (2.79%)
Voltage at Load End11.7 VLoss: 0.32 V (11.3 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.59 V (54.88%)5.4 V10.86 V (90.52%)230.5 WDrop/Amp High
12 AWG3.31 mm²20 A4.14 V (34.49%)7.9 V6.83 V (56.89%)144.8 WDrop/Amp High
10 AWG5.26 mm²30 A2.6 V (21.7%)9.4 V4.3 V (35.8%)91.1 WDrop/Amp High
8 AWG8.37 mm²50 A1.64 V (13.64%)10.4 V2.7 V (22.5%)57.3 WDrop/Amp High
6 AWG13.3 mm²65 A1.03 V (8.58%)11.0 V1.7 V (14.16%)36.0 WDrop/Amp High
4 AWG21.15 mm²85 A0.65 V (5.4%)11.4 V1.07 V (8.9%)22.7 WDrop/Amp High
3 AWG26.67 mm²100 A0.51 V (4.28%)11.5 V0.85 V (7.06%)18.0 W~ ≤5%
2 AWG33.62 mm²115 A0.41 V (3.4%)11.6 V0.67 V (5.6%)14.3 W~ ≤5%
1 AWG42.41 mm²130 A0.32 V (2.69%)11.7 V0.53 V (4.44%)11.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.26 V (2.13%)11.7 V0.42 V (3.52%)9.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.2 V (1.69%)11.8 V0.34 V (2.79%)7.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.16 V (1.34%)11.8 V0.27 V (2.21%)5.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.13 V (1.06%)11.9 V0.21 V (1.76%)4.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.11 V (0.9%)11.9 V0.18 V (1.49%)3.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.09 V (0.75%)11.9 V0.15 V (1.24%)3.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.08 V (0.64%)11.9 V0.13 V (1.06%)2.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.07 V (0.56%)11.9 V0.11 V (0.93%)2.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.45%)11.9 V0.09 V (0.74%)1.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.38%)12.0 V0.07 V (0.62%)1.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.3%)12.0 V0.06 V (0.5%)1.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.23%)12.0 V0.04 V (0.37%)0.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 30 feet one-way at 12V (DC), you need 1 AWG copper wire. This produces a voltage drop of 0.32V (2.69%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 0.34V (2.79%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.