🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.3V (2.48%)
Voltage at Load End11.7 VLoss: 0.34 V (11.8 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A32.93 V (274.39%)0.0 V54.31 V (452.62%)1152.5 WDrop/Amp High
12 AWG3.31 mm²20 A20.69 V (172.43%)0.0 V34.13 V (284.43%)724.2 WDrop/Amp High
10 AWG5.26 mm²30 A13.02 V (108.51%)0.0 V21.48 V (178.98%)455.7 WDrop/Amp High
8 AWG8.37 mm²50 A8.18 V (68.19%)3.8 V13.5 V (112.48%)286.4 WDrop/Amp High
6 AWG13.3 mm²65 A5.15 V (42.91%)6.9 V8.49 V (70.79%)180.2 WDrop/Amp High
4 AWG21.15 mm²85 A3.24 V (26.99%)8.8 V5.34 V (44.51%)113.3 WDrop/Amp High
3 AWG26.67 mm²100 A2.57 V (21.4%)9.4 V4.24 V (35.3%)89.9 WDrop/Amp High
2 AWG33.62 mm²115 A2.04 V (16.98%)10.0 V3.36 V (28.0%)71.3 WDrop/Amp High
1 AWG42.41 mm²130 A1.61 V (13.46%)10.4 V2.66 V (22.2%)56.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.28 V (10.67%)10.7 V2.11 V (17.6%)44.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.02 V (8.46%)11.0 V1.68 V (13.96%)35.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.81 V (6.71%)11.2 V1.33 V (11.07%)28.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.64 V (5.32%)11.4 V1.05 V (8.78%)22.4 WDrop/Amp High
250 kcmil126.7 mm²255 A0.54 V (4.5%)11.5 V0.89 V (7.43%)18.9 W~ ≤5%
300 kcmil152.0 mm²285 A0.45 V (3.75%)11.5 V0.74 V (6.19%)15.8 W~ ≤5%
350 kcmil177.3 mm²310 A0.39 V (3.22%)11.6 V0.64 V (5.31%)13.5 W~ ≤5%
400 kcmil202.7 mm²335 A0.34 V (2.82%)11.7 V0.56 V (4.64%)11.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.27 V (2.25%)11.7 V0.45 V (3.72%)9.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (1.88%)11.8 V0.37 V (3.1%)7.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.18 V (1.5%)11.8 V0.3 V (2.48%)6.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (1.13%)11.9 V0.22 V (1.86%)4.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 150 feet one-way at 12V (DC), you need 400 kcmil copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.3V (2.48%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.