⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 40 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.85%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 0.35V (2.95%)
Voltage at Load End11.7 VLoss: 0.34 V (12.0 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 40 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A8.78 V (73.17%)3.2 V14.48 V (120.7%)307.3 WDrop/Amp High
12 AWG3.31 mm²20 A5.52 V (45.98%)6.5 V9.1 V (75.85%)193.1 WDrop/Amp High
10 AWG5.26 mm²30 A3.47 V (28.93%)8.5 V5.73 V (47.73%)121.5 WDrop/Amp High
8 AWG8.37 mm²50 A2.18 V (18.18%)9.8 V3.6 V (29.99%)76.4 WDrop/Amp High
6 AWG13.3 mm²65 A1.37 V (11.44%)10.6 V2.27 V (18.88%)48.1 WDrop/Amp High
4 AWG21.15 mm²85 A0.86 V (7.2%)11.1 V1.42 V (11.87%)30.2 WDrop/Amp High
3 AWG26.67 mm²100 A0.68 V (5.71%)11.3 V1.13 V (9.41%)24.0 WDrop/Amp High
2 AWG33.62 mm²115 A0.54 V (4.53%)11.5 V0.9 V (7.47%)19.0 W~ ≤5%
1 AWG42.41 mm²130 A0.43 V (3.59%)11.6 V0.71 V (5.92%)15.1 W~ ≤5%
1/0 AWG53.49 mm²150 A0.34 V (2.85%)11.7 V0.56 V (4.69%)12.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.27 V (2.26%)11.7 V0.45 V (3.72%)9.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.21 V (1.79%)11.8 V0.35 V (2.95%)7.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.17 V (1.42%)11.8 V0.28 V (2.34%)6.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.14 V (1.2%)11.9 V0.24 V (1.98%)5.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.12 V (1.0%)11.9 V0.2 V (1.65%)4.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.1 V (0.86%)11.9 V0.17 V (1.42%)3.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.09 V (0.75%)11.9 V0.15 V (1.24%)3.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.07 V (0.6%)11.9 V0.12 V (0.99%)2.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.5%)11.9 V0.1 V (0.83%)2.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.4%)12.0 V0.08 V (0.66%)1.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.3%)12.0 V0.06 V (0.5%)1.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 40 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 40 feet one-way at 12V (DC), you need 1/0 AWG copper wire. This produces a voltage drop of 0.34V (2.85%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 0.35V (2.95%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.