🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1 AWGDrop: 3.11V (2.59%)
Voltage at Load End117.0 VLoss: 3.0 V (104.9 W)
Power & Breaker (125%)4.2 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A38.42 V (32.01%)81.6 V63.37 V (52.81%)1344.5 WDrop/Amp High
12 AWG3.31 mm²20 A24.14 V (20.12%)95.9 V39.82 V (33.18%)844.9 WDrop/Amp High
10 AWG5.26 mm²30 A15.19 V (12.66%)104.8 V25.06 V (20.88%)531.7 WDrop/Amp High
8 AWG8.37 mm²50 A9.55 V (7.96%)110.5 V15.75 V (13.12%)334.1 WDrop/Amp High
6 AWG13.3 mm²65 A6.01 V (5.01%)114.0 V9.91 V (8.26%)210.3 WDrop/Amp High
4 AWG21.15 mm²85 A3.78 V (3.15%)116.2 V6.23 V (5.19%)132.2 W~ ≤5%
3 AWG26.67 mm²100 A3.0 V (2.5%)117.0 V4.94 V (4.12%)104.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.38 V (1.98%)117.6 V3.92 V (3.27%)83.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.88 V (1.57%)118.1 V3.11 V (2.59%)65.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.49 V (1.24%)118.5 V2.46 V (2.05%)52.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.18 V (0.99%)118.8 V1.95 V (1.63%)41.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.94 V (0.78%)119.1 V1.55 V (1.29%)32.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.75 V (0.62%)119.3 V1.23 V (1.02%)26.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.63 V (0.53%)119.4 V1.04 V (0.87%)22.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.53 V (0.44%)119.5 V0.87 V (0.72%)18.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.45 V (0.38%)119.5 V0.74 V (0.62%)15.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.39 V (0.33%)119.6 V0.65 V (0.54%)13.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.32 V (0.26%)119.7 V0.52 V (0.43%)11.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.26 V (0.22%)119.7 V0.43 V (0.36%)9.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.21 V (0.18%)119.8 V0.35 V (0.29%)7.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.16 V (0.13%)119.8 V0.26 V (0.22%)5.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 175 feet one-way at 120V (1-Phase), you need 3 AWG copper wire. This produces a voltage drop of 3.0V (2.5%) and delivers 117.0V at the load.

What size aluminum wire is required for 35 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 3.11V (2.59%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.