🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)8 AWGDrop: 3.6V (3.0%)
Voltage at Load End117.8 VLoss: 2.18 V (76.4 W)
Power & Breaker (125%)4.2 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A8.78 V (7.32%)111.2 V14.48 V (12.07%)307.3 WDrop/Amp High
12 AWG3.31 mm²20 A5.52 V (4.6%)114.5 V9.1 V (7.58%)193.1 WDrop/Amp High
10 AWG5.26 mm²30 A3.47 V (2.89%)116.5 V5.73 V (4.77%)121.5 WDrop/Amp High
8 AWG8.37 mm²50 A2.18 V (1.82%)117.8 V3.6 V (3.0%)76.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.37 V (1.14%)118.6 V2.27 V (1.89%)48.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.86 V (0.72%)119.1 V1.42 V (1.19%)30.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.68 V (0.57%)119.3 V1.13 V (0.94%)24.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.54 V (0.45%)119.5 V0.9 V (0.75%)19.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.43 V (0.36%)119.6 V0.71 V (0.59%)15.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.34 V (0.28%)119.7 V0.56 V (0.47%)12.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.27 V (0.23%)119.7 V0.45 V (0.37%)9.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.21 V (0.18%)119.8 V0.35 V (0.3%)7.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.17 V (0.14%)119.8 V0.28 V (0.23%)6.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.14 V (0.12%)119.9 V0.24 V (0.2%)5.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.12 V (0.1%)119.9 V0.2 V (0.17%)4.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.1 V (0.09%)119.9 V0.17 V (0.14%)3.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.09 V (0.08%)119.9 V0.15 V (0.12%)3.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.07 V (0.06%)119.9 V0.12 V (0.1%)2.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.05%)119.9 V0.1 V (0.08%)2.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.04%)120.0 V0.08 V (0.07%)1.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.03%)120.0 V0.06 V (0.05%)1.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 40 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.18V (1.82%) and delivers 117.8V at the load.

What size aluminum wire is required for 35 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 3.6V (3.0%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.