🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.27%
Aluminum Wire (≤3% Drop)6 AWGDrop: 2.83V (2.36%)
Voltage at Load End117.3 VLoss: 2.73 V (95.5 W)
Power & Breaker (125%)4.2 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.98 V (9.15%)109.0 V18.1 V (15.09%)384.2 WDrop/Amp High
12 AWG3.31 mm²20 A6.9 V (5.75%)113.1 V11.38 V (9.48%)241.4 WDrop/Amp High
10 AWG5.26 mm²30 A4.34 V (3.62%)115.7 V7.16 V (5.97%)151.9 WDrop/Amp High
8 AWG8.37 mm²50 A2.73 V (2.27%)117.3 V4.5 V (3.75%)95.5 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.72 V (1.43%)118.3 V2.83 V (2.36%)60.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.08 V (0.9%)118.9 V1.78 V (1.48%)37.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.86 V (0.71%)119.1 V1.41 V (1.18%)30.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.68 V (0.57%)119.3 V1.12 V (0.93%)23.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.54 V (0.45%)119.5 V0.89 V (0.74%)18.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.43 V (0.36%)119.6 V0.7 V (0.59%)14.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.34 V (0.28%)119.7 V0.56 V (0.47%)11.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.27 V (0.22%)119.7 V0.44 V (0.37%)9.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.21 V (0.18%)119.8 V0.35 V (0.29%)7.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.18 V (0.15%)119.8 V0.3 V (0.25%)6.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.15 V (0.13%)119.8 V0.25 V (0.21%)5.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.11%)119.9 V0.21 V (0.18%)4.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.11 V (0.09%)119.9 V0.19 V (0.15%)3.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.08%)119.9 V0.15 V (0.12%)3.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.06%)119.9 V0.12 V (0.1%)2.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.05%)119.9 V0.1 V (0.08%)2.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.04%)120.0 V0.07 V (0.06%)1.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 50 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.73V (2.27%) and delivers 117.3V at the load.

What size aluminum wire is required for 35 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 2.83V (2.36%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.