🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 250 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.37V (3.1%)
Voltage at Load End11.7 VLoss: 0.3 V (10.5 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 250 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.88 V (457.32%)0.0 V90.52 V (754.37%)1920.8 WDrop/Amp High
12 AWG3.31 mm²20 A34.49 V (287.38%)0.0 V56.89 V (474.04%)1207.0 WDrop/Amp High
10 AWG5.26 mm²30 A21.7 V (180.84%)0.0 V35.8 V (298.31%)759.5 WDrop/Amp High
8 AWG8.37 mm²50 A13.64 V (113.65%)0.0 V22.5 V (187.47%)477.3 WDrop/Amp High
6 AWG13.3 mm²65 A8.58 V (71.52%)3.4 V14.16 V (117.98%)300.4 WDrop/Amp High
4 AWG21.15 mm²85 A5.4 V (44.98%)6.6 V8.9 V (74.19%)188.9 WDrop/Amp High
3 AWG26.67 mm²100 A4.28 V (35.67%)7.7 V7.06 V (58.83%)149.8 WDrop/Amp High
2 AWG33.62 mm²115 A3.4 V (28.29%)8.6 V5.6 V (46.67%)118.8 WDrop/Amp High
1 AWG42.41 mm²130 A2.69 V (22.43%)9.3 V4.44 V (37.0%)94.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.13 V (17.78%)9.9 V3.52 V (29.33%)74.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.69 V (14.11%)10.3 V2.79 V (23.27%)59.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.34 V (11.19%)10.7 V2.21 V (18.46%)47.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.06 V (8.87%)10.9 V1.76 V (14.64%)37.3 WDrop/Amp High
250 kcmil126.7 mm²255 A0.9 V (7.51%)11.1 V1.49 V (12.38%)31.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.75 V (6.26%)11.2 V1.24 V (10.32%)26.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.64 V (5.37%)11.4 V1.06 V (8.85%)22.5 WDrop/Amp High
400 kcmil202.7 mm²335 A0.56 V (4.69%)11.4 V0.93 V (7.74%)19.7 W~ ≤5%
500 kcmil253.4 mm²380 A0.45 V (3.75%)11.5 V0.74 V (6.19%)15.8 W~ ≤5%
600 kcmil304.0 mm²420 A0.38 V (3.13%)11.6 V0.62 V (5.16%)13.1 W~ ≤5%
750 kcmil380.0 mm²475 A0.3 V (2.5%)11.7 V0.5 V (4.13%)10.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (1.88%)11.8 V0.37 V (3.1%)7.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 250 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 250 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.3V (2.5%) and delivers 11.7V at the load.

What size aluminum wire is required for 35 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.37V (3.1%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.