🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.49%
Aluminum Wire (≤3% Drop)1 AWGDrop: 5.38V (2.59%)
Voltage at Load End202.8 VLoss: 5.19 V (314.6 W)
Power & Breaker (125%)12.61 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A66.54 V (31.99%)141.5 V109.75 V (52.77%)4033.6 WDrop/Amp High
12 AWG3.31 mm²20 A41.81 V (20.1%)166.2 V68.97 V (33.16%)2534.7 WDrop/Amp High
10 AWG5.26 mm²30 A26.31 V (12.65%)181.7 V43.4 V (20.87%)1595.0 WDrop/Amp High
8 AWG8.37 mm²50 A16.53 V (7.95%)191.5 V27.27 V (13.11%)1002.4 WDrop/Amp High
6 AWG13.3 mm²65 A10.41 V (5.0%)197.6 V17.16 V (8.25%)630.8 WDrop/Amp High
4 AWG21.15 mm²85 A6.54 V (3.15%)201.5 V10.79 V (5.19%)396.7 W~ ≤5%
3 AWG26.67 mm²100 A5.19 V (2.49%)202.8 V8.56 V (4.12%)314.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.12 V (1.98%)203.9 V6.79 V (3.26%)249.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.26 V (1.57%)204.7 V5.38 V (2.59%)197.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.59 V (1.24%)205.4 V4.27 V (2.05%)156.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.05 V (0.99%)205.9 V3.39 V (1.63%)124.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.63 V (0.78%)206.4 V2.69 V (1.29%)98.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.29 V (0.62%)206.7 V2.13 V (1.02%)78.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.09 V (0.53%)206.9 V1.8 V (0.87%)66.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.91 V (0.44%)207.1 V1.5 V (0.72%)55.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.78 V (0.38%)207.2 V1.29 V (0.62%)47.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.68 V (0.33%)207.3 V1.13 V (0.54%)41.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.55 V (0.26%)207.5 V0.9 V (0.43%)33.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.22%)207.5 V0.75 V (0.36%)27.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.18%)207.6 V0.6 V (0.29%)22.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.13%)207.7 V0.45 V (0.22%)16.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 350 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.19V (2.49%) and delivers 202.8V at the load.

What size aluminum wire is required for 35 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 5.38V (2.59%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.