🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.58V (2.99%)
Voltage at Load End117.1 VLoss: 2.9 V (1086.2 W)
Power & Breaker (125%)45.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A529.19 V (440.99%)0.0 V872.91 V (727.43%)198445.1 WDrop/Amp High
12 AWG3.31 mm²20 A332.54 V (277.12%)0.0 V548.54 V (457.11%)124702.7 WDrop/Amp High
10 AWG5.26 mm²30 A209.26 V (174.38%)0.0 V345.18 V (287.65%)78472.6 WDrop/Amp High
8 AWG8.37 mm²50 A131.51 V (109.59%)0.0 V216.92 V (180.77%)49314.9 WDrop/Amp High
6 AWG13.3 mm²65 A82.76 V (68.97%)37.2 V136.52 V (113.76%)31035.0 WDrop/Amp High
4 AWG21.15 mm²85 A52.04 V (43.37%)68.0 V85.85 V (71.54%)19516.1 WDrop/Amp High
3 AWG26.67 mm²100 A41.27 V (34.39%)78.7 V68.08 V (56.73%)15476.8 WDrop/Amp High
2 AWG33.62 mm²115 A32.74 V (27.28%)87.3 V54.01 V (45.0%)12277.4 WDrop/Amp High
1 AWG42.41 mm²130 A25.95 V (21.63%)94.0 V42.81 V (35.68%)9732.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.58 V (17.15%)99.4 V33.94 V (28.29%)7716.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.32 V (13.6%)103.7 V26.93 V (22.44%)6121.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.95 V (10.79%)107.1 V21.36 V (17.8%)4855.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.27 V (8.56%)109.7 V16.94 V (14.11%)3850.4 WDrop/Amp High
250 kcmil126.7 mm²255 A8.69 V (7.24%)111.3 V14.33 V (11.94%)3257.8 WDrop/Amp High
300 kcmil152.0 mm²285 A7.24 V (6.03%)112.8 V11.95 V (9.95%)2715.6 WDrop/Amp High
350 kcmil177.3 mm²310 A6.21 V (5.17%)113.8 V10.24 V (8.53%)2328.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.43 V (4.53%)114.6 V8.96 V (7.46%)2036.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.34 V (3.62%)115.7 V7.17 V (5.97%)1628.9 W~ ≤5%
600 kcmil304.0 mm²420 A3.62 V (3.02%)116.4 V5.97 V (4.98%)1357.8 W~ ≤5%
750 kcmil380.0 mm²475 A2.9 V (2.41%)117.1 V4.78 V (3.98%)1086.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.17 V (1.81%)117.8 V3.58 V (2.99%)814.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 225 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.9V (2.41%) and delivers 117.1V at the load.

What size aluminum wire is required for 375 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.58V (2.99%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.