⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 400 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.52V (2.65%)
Voltage at Load End202.4 VLoss: 5.57 V (3620.8 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 400 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A814.74 V (391.7%)0.0 V1343.93 V (646.12%)529187.0 WDrop/Amp High
12 AWG3.31 mm²20 A511.98 V (246.14%)0.0 V844.53 V (406.02%)332540.5 WDrop/Amp High
10 AWG5.26 mm²30 A322.18 V (154.89%)0.0 V531.44 V (255.5%)209260.3 WDrop/Amp High
8 AWG8.37 mm²50 A202.47 V (97.34%)5.5 V333.98 V (160.57%)131506.5 WDrop/Amp High
6 AWG13.3 mm²65 A127.42 V (61.26%)80.6 V210.18 V (101.05%)82760.1 WDrop/Amp High
4 AWG21.15 mm²85 A80.13 V (38.52%)127.9 V132.17 V (63.54%)52043.0 WDrop/Amp High
3 AWG26.67 mm²100 A63.54 V (30.55%)144.5 V104.81 V (50.39%)41271.4 WDrop/Amp High
2 AWG33.62 mm²115 A50.41 V (24.23%)157.6 V83.15 V (39.97%)32739.7 WDrop/Amp High
1 AWG42.41 mm²130 A39.96 V (19.21%)168.0 V65.91 V (31.69%)25954.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.68 V (15.23%)176.3 V52.26 V (25.12%)20577.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.13 V (12.08%)182.9 V41.46 V (19.93%)16323.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.93 V (9.58%)188.1 V32.88 V (15.81%)12948.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.81 V (7.6%)192.2 V26.08 V (12.54%)10267.8 WDrop/Amp High
250 kcmil126.7 mm²255 A13.38 V (6.43%)194.6 V22.06 V (10.61%)8687.5 WDrop/Amp High
300 kcmil152.0 mm²285 A11.15 V (5.36%)196.9 V18.39 V (8.84%)7241.5 WDrop/Amp High
350 kcmil177.3 mm²310 A9.56 V (4.6%)198.4 V15.77 V (7.58%)6208.2 WDrop/Amp High
400 kcmil202.7 mm²335 A8.36 V (4.02%)199.6 V13.79 V (6.63%)5430.2 WDrop/Amp High
500 kcmil253.4 mm²380 A6.69 V (3.22%)201.3 V11.03 V (5.3%)4343.8 W~ ≤5%
600 kcmil304.0 mm²420 A5.57 V (2.68%)202.4 V9.2 V (4.42%)3620.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.46 V (2.14%)203.5 V7.36 V (3.54%)2896.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.34 V (1.61%)204.7 V5.52 V (2.65%)2172.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 400 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 400 feet one-way at 208V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 5.57V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 375 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.52V (2.65%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.