🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 750 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)21× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.94V (99.54%)
Voltage at Load End11.7 VLoss: 0.34 V (129.3 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 750 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1763.96 V (14699.64%)0.0 V2909.7 V (24247.54%)661483.8 WDrop/Amp High
12 AWG3.31 mm²20 A1108.47 V (9237.24%)0.0 V1828.45 V (15237.12%)415675.6 WDrop/Amp High
10 AWG5.26 mm²30 A697.53 V (5812.79%)0.0 V1150.61 V (9588.38%)261575.3 WDrop/Amp High
8 AWG8.37 mm²50 A438.35 V (3652.96%)0.0 V723.08 V (6025.67%)164383.1 WDrop/Amp High
6 AWG13.3 mm²65 A275.87 V (2298.89%)0.0 V455.05 V (3792.1%)103450.1 WDrop/Amp High
4 AWG21.15 mm²85 A173.48 V (1445.64%)0.0 V286.16 V (2384.63%)65053.7 WDrop/Amp High
3 AWG26.67 mm²100 A137.57 V (1146.43%)0.0 V226.93 V (1891.07%)51589.3 WDrop/Amp High
2 AWG33.62 mm²115 A109.13 V (909.44%)0.0 V180.02 V (1500.15%)40924.6 WDrop/Amp High
1 AWG42.41 mm²130 A86.51 V (720.94%)0.0 V142.71 V (1189.22%)32442.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A68.59 V (571.61%)0.0 V113.15 V (942.88%)25722.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A54.41 V (453.44%)0.0 V89.76 V (747.96%)20404.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A43.16 V (359.67%)0.0 V71.19 V (593.28%)16185.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A34.23 V (285.22%)0.0 V56.46 V (470.47%)12834.8 WDrop/Amp High
250 kcmil126.7 mm²255 A28.96 V (241.32%)0.0 V47.77 V (398.07%)10859.4 WDrop/Amp High
300 kcmil152.0 mm²285 A24.14 V (201.15%)0.0 V39.82 V (331.81%)9051.9 WDrop/Amp High
350 kcmil177.3 mm²310 A20.69 V (172.45%)0.0 V34.14 V (284.46%)7760.2 WDrop/Amp High
400 kcmil202.7 mm²335 A18.1 V (150.84%)0.0 V29.86 V (248.82%)6787.8 WDrop/Amp High
500 kcmil253.4 mm²380 A14.48 V (120.66%)0.0 V23.88 V (199.03%)5429.7 WDrop/Amp High
600 kcmil304.0 mm²420 A12.07 V (100.58%)0.0 V19.91 V (165.9%)4525.9 WDrop/Amp High
750 kcmil380.0 mm²475 A9.66 V (80.46%)2.3 V15.93 V (132.72%)3620.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.24 V (60.34%)4.8 V11.94 V (99.54%)2715.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 750 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 750 feet one-way at 12V (DC), you need 21× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.87%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.94V (99.54%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.