🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.59%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.52V (0.73%)
Voltage at Load End477.2 VLoss: 2.84 V (2092.8 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A519.39 V (108.21%)0.0 V856.76 V (178.49%)382337.6 WDrop/Amp High
12 AWG3.31 mm²20 A326.39 V (68.0%)153.6 V538.39 V (112.16%)240260.5 WDrop/Amp High
10 AWG5.26 mm²30 A205.39 V (42.79%)274.6 V338.79 V (70.58%)151190.5 WDrop/Amp High
8 AWG8.37 mm²50 A129.07 V (26.89%)350.9 V212.91 V (44.36%)95013.4 WDrop/Amp High
6 AWG13.3 mm²65 A81.23 V (16.92%)398.8 V133.99 V (27.91%)59794.2 WDrop/Amp High
4 AWG21.15 mm²85 A51.08 V (10.64%)428.9 V84.26 V (17.55%)37601.1 WDrop/Amp High
3 AWG26.67 mm²100 A40.51 V (8.44%)439.5 V66.82 V (13.92%)29818.6 WDrop/Amp High
2 AWG33.62 mm²115 A32.13 V (6.69%)447.9 V53.01 V (11.04%)23654.4 WDrop/Amp High
1 AWG42.41 mm²130 A25.47 V (5.31%)454.5 V42.02 V (8.75%)18751.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.2 V (4.21%)459.8 V33.32 V (6.94%)14867.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.02 V (3.34%)464.0 V26.43 V (5.51%)11793.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.71 V (2.65%)467.3 V20.96 V (4.37%)9354.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.08 V (2.1%)469.9 V16.62 V (3.46%)7418.5 WDrop/Amp High
250 kcmil126.7 mm²255 A8.53 V (1.78%)471.5 V14.07 V (2.93%)6276.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.11 V (1.48%)472.9 V11.72 V (2.44%)5232.0 WDrop/Amp High
350 kcmil177.3 mm²310 A6.09 V (1.27%)473.9 V10.05 V (2.09%)4485.4 WDrop/Amp High
400 kcmil202.7 mm²335 A5.33 V (1.11%)474.7 V8.79 V (1.83%)3923.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.26 V (0.89%)475.7 V7.03 V (1.47%)3138.4 WDrop/Amp High
600 kcmil304.0 mm²420 A3.55 V (0.74%)476.4 V5.86 V (1.22%)2616.0 WDrop/Amp High
750 kcmil380.0 mm²475 A2.84 V (0.59%)477.2 V4.69 V (0.98%)2092.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.13 V (0.44%)477.9 V3.52 V (0.73%)1569.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 225 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.84V (0.59%) and delivers 477.2V at the load.

What size aluminum wire is required for 425 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.52V (0.73%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.